LIBERTY, MO ·
OSHA Inspection: EVEREST CASTER & WHEELS, LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of EVEREST CASTER & WHEELS, LLC in 17815 FOSTER ROAD #146, LIBERTY, MO 64068 (NAICS 493110). OSHA activity number 339883373.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EVEREST CASTER & WHEELS, LLC
- Site address
- 17815 FOSTER ROAD #146
- City
- LIBERTY
- State
- MO
- ZIP
- 64068
- Mailing
- 17815 FOSTER ROAD #146, LIBERTY, MO 64068
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 12
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.37 A03
- Issued
- Aug 19, 2014
- Abate by
- Oct 6, 2014
- Penalty
- Initial $2,400 · Current $0 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) In the warehouse - Employees were working in areas where wooden crates, weighing 1733kgs, were obstructing the emergency exit. Abatement certification for this item is required.
Recent events (2)
- · I (O) $0
- · Z (S) $2400
1910.157 C04
- Issued
- Aug 19, 2014
- Abate by
- Oct 6, 2014
- Penalty
- Initial $2,400 · Current $1,200 Reduced
General-duty citation text
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition: In the warehouse - Employees were working in an area where only one "Amerex" type 1-A:10-B:C portable fire extinguisher was available, but was observed to have zero charge and no other fire protection system was available. Abatement certification for this item is required.
Recent events (2)
- · I (S) $1200
- · Z (S) $2400
1910.157 D01
- Issued
- Aug 19, 2014
- Abate by
- Oct 6, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(d)(1): Portable fire extinguishers were not selected based on the classes of anticipated workplace fires and on the size and degree of hazard that would affect their use: a) In the warehouse - Employees were working in an area, approximately 43,000 square feet, where only one "Amerex" type 1-A:10-B:C portable fire extinguisher was available for employees and no other fire protection system was available. Abatement certification for this item is required.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.157 D02
- Issued
- Aug 19, 2014
- Abate by
- Oct 6, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(d)(2): Portable fire extinguishers for use on Class A fires were not distributed so that the travel distance for employees to any extinguisher was 75 feet or less: a) In the warehouse - Employees were working in areas where only one "Amerex" type 1-A:10-B:C portable fire extinguisher was available in the warehouse, approximately 43,000 square feet, creating a travel distance of several hundred feet across the warehouse where no other fire protection system was available. Abatement certification is required for this item.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.178 G02
- Issued
- Aug 19, 2014
- Abate by
- Oct 31, 2014
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.178(g)(2): Battery charging apparatus for industrial trucks located in battery changing and charging installation was not protected from damage by trucks: a) In the warehouse - Employees were operating two industrial fork trucks where three battery chargers ("Ferro Five" S/N: JPIU937335, 24 volts/50 amperes; "Exide Gold" S/N: DA112988, 36 volts/152 amperes; and "Lifeguard" S/N: 99U15693, 36 volts/135 amperes) were not protected from damage by the industrial fork trucks, creating contact with electricity hazards. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1,000.00 IN ACCORDANCE WITH 29 CFR 1903.19
Recent events (2)
- · I (S) $1400
- · Z (S) $2800
1910.212 A01
- Issued
- Aug 19, 2014
- Abate by
- Oct 31, 2014
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a) In the warehouse - Employees were using a "Jet" floor drill press (S/N: 10050311) to bore out wheel holes where the rotating chuck on the drill press was not guarded against employee contact. Abatement certification for this item is required.
Recent events (2)
- · I (S) $1000
- · Z (S) $2000
1910.212 B
- Issued
- Aug 19, 2014
- Abate by
- Oct 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving: a) In the warehouse - Employees where using a "Jet" floor drill press (S/N: 10050311), to bore out wheel holes, that was not fastened to the floor to prevent the floor drill press from being pulled over onto an employee. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1,000.00 IN ACCORDANCE WITH 29 CFR 1903.19
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 G01
- Issued
- Aug 19, 2014
- Abate by
- Oct 6, 2014
- Penalty
- Initial $1,200 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) In the office - Two 480 volt/ 200 ampere electrical panels were blocked by a large cardboard box full of miscellaneous office supplies, causing hazards with delay in accessibility during an emergency. Abatement certification for this item is required.
Recent events (2)
- · I (S) $0
- · Z (S) $1200
1910.305 G01 IV A
- Issued
- Aug 19, 2014
- Abate by
- Oct 6, 2014
- Penalty
- Initial $2,400 · Current $1,200 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) In the warehouse - Employees were using a flexible cord as permanent wiring to power appliances, such as but not limited to, microwave and coffee maker, from outlet (~125 volts/15 amperes) creating contact with electricity hazards. Everest Caster & Wheels, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 944909, citation number 1, item number 3 and was affirmed as a final order on 12/03/2013, with respect to a workplace located at 17815 Foster Rd #146 in Liberty, MO 64068.
Recent events (2)
- · I (S) $1200
- · Z (R) $2400
More inspections at Everest Caster & Wheels, LLC
View Everest Caster & Wheels, LLC's full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339883373.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.