OSHA Inspection: BRASS ALIGNMENT, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BRASS ALIGNMENT, LLC in 111 ROSE STREET, WILLIAMSPORT, PA 17701 (NAICS 811111). OSHA activity number 339891558.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Brass Alignment, LLC for free Get an email when a new federal OSHA severe-injury report for Brass Alignment, LLC is published. One employer, no account, unsubscribe in one click.
Site address
111 ROSE STREET
City
WILLIAMSPORT
State
PA
ZIP
17701
Mailing
111 ROSE STREET, WILLIAMSPORT, PA 17701
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811111
Employees
16
Ownership type
Private (A)

3 citations on file for this inspection.

1910.303 G01

Serious Gravity 1 2 instances 7 exposed
Issued
Dec 8, 2014
Abate by
Dec 26, 2014
Penalty
Initial $1,200 · Current $900 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment.  (a) East wall of the Suspension Shop, 111 Rose Street, Williamsport, PA - Employee access to overcurrent devices (electrical panels) for the overhead lights, exhaust fans, and auxiliary equipment was blocked by a work bench, boxes, equipment and weights. Employees were exposed to slips, trips and falls and the hazards associated with being unable to de-energize equipment in the event of an emergency, as observed on or about June 19, 2013.    (b) East wall of the Trailer Shop, 111 Rose Street, Williamsport, PA - Employee access to overcurrent devices (electrical panels) for the overhead lights and auxiliary equipment was blocked by a cabinet and work bench. Employees were exposed to slips, trips and falls and the hazards associated with being unable to de-energize equipment in the event of an emergency, as observed on or about June 19, 2013.    In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
  • · I (S) $900
  • · Z (S) $1200

1910.305 B02

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 8, 2014
Abate by
Dec 26, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  (a) East wall of the Trailer Shop, 111 Rose Street, Williamsport, PA - Employees operated and started electrical equipment near exposed energized conductors (120V) in an uncovered electrical outlet box. Employees were exposed to contact with electrical current, as observed on or about August 8, 2014.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.212 A01

Other-than-serious 1 instance 3 exposed
Issued
Dec 8, 2014
Abate by
Dec 26, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  a) Suspension Shop, 111 Rose Street, Williamsport, PA - Employees operated a Canedy-Otto Drill Press (Serial No. C1170) that did not have guarding protecting employees from the rotating shaft and at the point of operation. Employees were exposed to a caught-in hazard, on or about August 8, 2014.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339891558.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.