Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: OMEGA INDUSTRIAL SERVICES

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of OMEGA INDUSTRIAL SERVICES in 5500 UNITED DRIVE SE, SMYRNA, GA 30082 (NAICS 238210). OSHA activity number 339902009.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Omega Industrial Services for free Get an email when a new federal OSHA severe-injury report for Omega Industrial Services is published. One employer, no account, unsubscribe in one click.
Site address
5500 UNITED DRIVE SE
City
SMYRNA
State
GA
ZIP
30082
Mailing
PO BOX 898, LITHIA SPRINGS, GA 30122
Inspection type
Unprogrammed Other (J)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
16
Ownership type
Private (A)

4 citations on file for this inspection.

1910.332 B01

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Oct 22, 2014
Abate by
Nov 18, 2014
Penalty
Initial $2,800 · Current $0 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  a.  5500 United Drive SE, Smyrna GA - The qualified and unqualified employees were not familiar with and trained in safety-related work practices when working near or on live electrical parts or potential live parts when working in the Motor Control Center for the conveyor system thereby exposing the employees to shock and arc flash/blast hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $2800

1910.333 A

Other-than-serious 1 instance 2 exposed
Issued
Oct 22, 2014
Abate by
Nov 18, 2014
Penalty
Initial $2,800 · Current $1,200 Reduced
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:     a.  5500 United Drive SE, Smyrna GA - Safety-related work practices were not used and available to employees who worked on or near live electrical parts, in that employees were exposed to shock and arc flash/blast hazards because employees were not provided with personal protective equipment.
Recent events (2)
  • · I (O) $1200
  • · Z (S) $2800

1910.335 A01 I

Other-than-serious 1 instance 2 exposed
Issued
Oct 22, 2014
Abate by
Nov 18, 2014
Penalty
Initial $2,800 · Current $0 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    a. 5500 United Drive SE, Smyrna GA  - The employees were not provided with personal protective equipment commensurate with the parts of the body exposed to shock and arc flash/blast hazards thereby exposing the employees to shock arc flash/blast hazards.
Recent events (2)
  • · I (O) $0
  • · Z (S) $2800

1910.333 A01

Other-than-serious 1 instance 2 exposed
Issued
Oct 22, 2014
Abate by
Nov 18, 2014
Penalty
Initial $2,800 · Current $1,200 Reduced
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs     a.  5500 United Drive SE, Smyrna GA - Live parts to which an employee may be exposed were not deenergized or other authorized means used for employee protection from shock and arc flash/blast hazards before the employee worked on or near live parts.
Recent events (2)
  • · I (O) $1200
  • · Z (S) $2800

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339902009.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.