BENTON, IL ·
OSHA Inspection: BIO FUELS BY AMERICAN FARMERS & VETERANS (BFAFV) LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BIO FUELS BY AMERICAN FARMERS & VETERANS (BFAFV) LLC in 10165 SUGAR CREEK ROAD, BENTON, IL 62812 (NAICS 325193). OSHA activity number 339904765.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BIO FUELS BY AMERICAN FARMERS & VETERANS (BFAFV) LLC
- Site address
- 10165 SUGAR CREEK ROAD
- City
- BENTON
- State
- IL
- ZIP
- 62812
- Mailing
- 2034 ST. CLAIR AVENUE, EAST SAINT LOUIS, IL 62205
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325193
- Employees
- 6
- Ownership type
- A
Citations
7 citations on file for this inspection.
1903.19 C01
- Issued
- Mar 20, 2015
- Abate by
- Apr 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1903.19(c)(1): The employer did not certify to OSHA, within 10 calendar days after the abatement date, that the cited violation had been abated: a) For Citation 1, Item 1, issued on 1/28/2015 with an abatement date of 2/24/2015, the employer did not certify the complete abatement of the cited violation. b) For Citation 1, Item 2, issued on 1/28/2015 with an abatement date of 2/24/2015, the employer did not certify the complete abatement of the cited violation. c) For Citation 1, Item 3, issued on 1/28/2015 with an abatement date of 2/24/2015, the employer did not certify the complete abatement of the cited violation. d) For Citation 1, Item 4, issued on 1/28/2015 with an abatement date of 2/24/2015, the employer did not certify the complete abatement of the cited violation. e) For Citation 1, Item 5, issued on 1/28/2015 with an abatement date of 2/3/2015, the employer did not certify the complete abatement of the cited violation. f) For Citation 1, Item 6, issued on 1/28/2015 with an abatement date of 2/24/2015, the employer did not certify the complete abatement of the cited violation.
Recent events (1)
- · Z (O) $0
1910.23 E01
- Issued
- Jan 28, 2015
- Abate by
- Feb 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(e)(1): The railing did not consist of top rail, intermediate rail, and posts, and did not have a vertical height of 42 inches nominal from upper surface of top rail to floor, platform, runway, or ramp level: a) Employees were exposed to falls of greater than 4 feet while accessing the walkway along the top of the 8 fermenter tanks. The employer had not installed a complete standard railing (or the equivalent) to protect employees from falls, the mid rail was missing.
Recent events (1)
- · Z (S) $0
1910.23 E03 V B
- Issued
- Jan 28, 2015
- Abate by
- Feb 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(e)(3)(v)(b): Railing construction type, size and/or arrangement did not meet the minimum requirement of strength to withstand at least 200 pounds top rail pressure: a) Employees were exposed to falls of greater than 4 feet while accessing the walkway along the top of the 8 fermenter tanks. The top chain component was connected to the post with carabiner rated at 150 pounds. Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (1)
- · Z (S) $0
1910.212 A05
- Issued
- Jan 28, 2015
- Abate by
- Feb 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(5): Fan blade guards, where the periphery of the blades was less than seven feet above the floor or working level, had openings larger than one half inch: a) On the west side of facility, on the cart mounted fan blower, the steel grating guard covering the squirrel cage blades had 2 to 3 inch rectangular openings.
Recent events (1)
- · Z (S) $0
1910.303 F02
- Issued
- Jan 28, 2015
- Abate by
- Feb 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) North side of facility, in the Electrical Room, employees were exposed to electrical hazards, the 240 volt electrical box electrical disconnect breakers were not marked.
Recent events (1)
- · Z (S) $0
1910.305 B01 II
- Issued
- Jan 28, 2015
- Abate by
- Feb 3, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) North side of facility, in the Electrical Room, employees were exposed to electrical hazards, due to a main 240 volt electrical box front panel did not completely cover the internal components. A several inch open space existed between the cover perimeter and the panel box frame.
Recent events (1)
- · Z (S) $0
1910.305 B02 I
- Issued
- Jan 28, 2015
- Abate by
- Feb 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) In the second floor Lab, a 110 volt electrical receptacle was missing its faceplate, exposing the inner electrical wiring connections.
Recent events (1)
- · Z (S) $0
More inspections at BIO Fuels by American Farmers & Veterans (Bfafv) LLC
View BIO Fuels by American Farmers & Veterans (Bfafv) LLC's full OSHA safety record →
More inspections in this industry (NAICS 325193)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339904765.