Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: A & D TIMBER COMPANY INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of A & D TIMBER COMPANY INC. in 465 THELMA ANDREWS ROAD, WIGGINS, MS 39577 (NAICS 113310). OSHA activity number 339916926.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch A & D Timber Company INC. — free Get an email when a new federal OSHA severe-injury report for A & D Timber Company INC. is published. One employer, no account, unsubscribe in one click.
Site address
465 THELMA ANDREWS ROAD
City
WIGGINS
State
MS
ZIP
39577
Mailing
P.O. BOX 550, WIGGINS, MS 39577
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
113310
Employees
25
Ownership type
A

10 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 30, 2014
Abate by
Nov 19, 2014
Penalty
Initial $2,000 · Current $1,200 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to struck by hazards of plastic shrapnel pieces from the rupture of PVC pipe used for compressed air:  a) Maintenance shop - On or about August 18, 2014, polyvinyl chloride (PVC) pipe was used along the wall for compressed air.  Reference for PVC pipe -- American Society of Mechanical Engineers, ASMS B31.3 - 2010, Section A323.4.2 (a),(3)
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1910.212 A05

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 30, 2014
Abate by
Nov 12, 2014
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.212(a)(5): Fan blade guard(s) were not provided where the periphery of the blades was less than seven feet from the floor or working level:  a) Maintenance shop - On or about August 18, 2014, a 4 foot by 4 foot box fan sitting on the floor did not have a guard on the back side.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1910.219 D01

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 30, 2014
Abate by
Nov 19, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):  a) Maintenance shop - On or about August 18, 2014, the pulleys on 4 foot by 4 foot box fan were not guarded.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 E03 I

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 30, 2014
Abate by
Nov 19, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.219(e)(3)(i): Vertical or inclined belt(s) were not enclosed by guard(s) conforming to the requirements specified at 29 CFR 1910.219(m) and (o):  a) Maintenance shop - On or about August 18, 2014, a 4 foot by 4 foot box fan sitting on the floor did not have a guard over the belts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 2 instances 2 exposed
Issued
Oct 30, 2014
Abate by
Nov 12, 2014
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  a) Maintenance shop - On or about August 18, 2014, a circuit breaker panel was missing covers for some of the slots.  b) Maintenance shop - On or about August 18, 2014, in the maintenance shop parts room, a 2 x 4 receptacle box was missing a cover plate.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1910.305 G02 II

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 30, 2014
Abate by
Nov 19, 2014
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap:  a) Maintenance shop - On or about August 18, 2014, a 4 foot by 4 foot box fan sitting on the floor had a splice in the flexible cord going to the fan. The splice did not have equivalent outer insulation as the original flexible cord and the color coding of the wires were not consistent.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1910.305 G02 III

Serious Gravity 5 2 instances 3 exposed
Issued
Oct 30, 2014
Abate by
Nov 19, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  a) Maintenance shop - On or about August 18, 2014, a 4 foot by 4 foot box fan sitting on the floor did not have any strain relief for the flexible cord going into the motor.  b) Maintenance shop - On or about August 18, 2014, an extension cord for the electric welder did not have any strain relief for the flexible cord entering the receptacle end.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01

Serious Gravity 5 1 instance 25 exposed
Issued
Oct 30, 2014
Abate by
Dec 18, 2014
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:  a) Maintenance shop - On or about August 18, 2014, there was no written hazard communication program, MSDS (SDS), labeling of containers of hazardous chemicals, and employee training for chemicals such as but not limited to: battery acid, fuels and oils for vehicles, log handling equipment, welding materials, and etc.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1910.303 F02

Other-than-serious 1 instance 3 exposed
Issued
Oct 30, 2014
Abate by
Nov 19, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) Maintenance shop - On or about August 18, 2014, employees were exposed to electrical hazards and LO/TO hazards because a circuit breaker panel in the storage room and another one in the work room were not labeled as to its purpose.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 3 exposed
Issued
Oct 30, 2014
Abate by
Nov 19, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less was used for storage:  a) Maintenance shop - On or about August 18, 2014, the circuit breaker panel in the work room had several gasoline powered equipment, a box and a bucket of materials stored in front of it.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View A & D Timber Company INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339916926.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.