Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KAMEHAMEHA SCHOOLS

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of KAMEHAMEHA SCHOOLS in 1887 MAKUAKANE STREET, HONOLULU, HI 96817 (NAICS 611110). OSHA activity number 339920399.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kamehameha Schools — free Get an email when a new federal OSHA severe-injury report for Kamehameha Schools is published. One employer, no account, unsubscribe in one click.
Establishment
KAMEHAMEHA SCHOOLS
Site address
1887 MAKUAKANE STREET
City
HONOLULU
State
HI
ZIP
96817
Mailing
1887 MAKUAKANE STREET, HONOLULU, HI 96817
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
611110
Employees
1500
Ownership type
A

5 citations on file for this inspection.

1910.101 B

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 7, 2015
Penalty
Initial $3,000 · Current $3,000
29 CFR 1910.101(b):  Section 3.4.4, of the Compressed Gas Association Pamphlet P-1 1965, as adopted by 29 CFR 1910.101(b):  Compressed gas cylinder(s) were not properly supported to prevent them from being knocked over:   a. On September 3, 2014, in the electrical plumbing shop, acetylene compressed gas cylinders were not secured to prevent from being knocked over.
Recent events (3)
  • — F (S) $3000
  • — C (S) $3000
  • — Z (S) $3000

1910.253 B04 III

Serious Gravity 1 1 instance 1 exposed
Issued
Jan 7, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:   a. On September 3, 2014, in the welding shop, oxygen cylinders were not separated from fuel-gas cylinders by a minimum distance of 20 feet or by a noncombustible barrier.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.132 A

Serious Gravity 5 2 instances 5 exposed
Issued
Jan 7, 2015
Abate by
Jan 27, 2015
Penalty
Initial $5,000 · Current $5,000
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered:  a. On July 24, 2014, throughout the facility, chemical protective clothing such as an apron and footwear was not available and/or used by employees dispensing and or transferring a caustic chemical.  b. On July 24, 2014, in the restrooms, chemical protective clothing such as an apron and footwear was not available and/or used by employees applying a caustic chemical.
Recent events (3)
  • — F (S) $5000
  • — C (S) $5000
  • — Z (S) $5000

1910.1200 H03 III

Serious Gravity 5 1 instance 6 exposed
Issued
Jan 7, 2015
Penalty
Initial $5,000 · Current $5,000
29 CFR 1910.1200(h)(3)(iii): Employee training did not include the measures employees can take to protect themselves from chemical hazards, including specific procedures the employer had implemented to protect employees from exposure to hazardous chemicals, such as appropriate work practices, emergency procedures and personal protective equipment to be used:  a. On July 24, 2014, the employer did not train employees on chemical hazards and measures to protect themselves from the hazards, when using chemicals to include but not limited to, Heavy Duty Non-Butyl Floor Stripper.
Recent events (3)
  • — F (S) $5000
  • — C (S) $5000
  • — Z (S) $5000

1910.303 F02

Other-than-serious 1 instance 1 exposed
Issued
Jan 7, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a. On September 3, 2014, in the electrical/plumbing shop, the employer did not ensure that the electrical panel disconnecting means were labeled and marked to indicate its purpose.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

View Kamehameha Schools's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339920399.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.