Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BIOGEN IDEC, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of BIOGEN IDEC, INC. in 14 CAMBRIDGE CENTER, CAMBRIDGE, MA 02142 (NAICS 325412). OSHA activity number 339942906.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Biogen Idec, INC. — free Get an email when a new federal OSHA severe-injury report for Biogen Idec, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
BIOGEN IDEC, INC.
Site address
14 CAMBRIDGE CENTER
City
CAMBRIDGE
State
MA
ZIP
02142
Mailing
14 CAMBRIDGE CENTER, CAMBRIDGE, MA 02142
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325412
Employees
4000
Ownership type
A

2 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Sep 22, 2014
Abate by
Oct 25, 2014
Penalty
Initial $3,750 · Current $3,750
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Location - 14 Cambridge Center, Cambridge, MA (Interstitial Space):  On or about 8/31/2014, armored cable was not secured and supported at interval in accordance with its listing and labeling (Ref. NFPA 70 Article 320).  (b) Location - 14 Cambridge Center, Cambridge, MA (Interstitial Space):  On or about 8/31/2014, an electrical junction box was not mounted in accordance with its listing and labeling (Ref. NFPA 70 Article 314).
Recent events (2)
  • — I (S) $3750
  • — Z (S) $3750

1910.303 G02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 22, 2014
Abate by
Oct 25, 2014
Penalty
Initial $3,750 · Current $3,750
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage:  (a) Location - 14 Cambridge Center, Cambridge, MA (Interstitial Space):  On or about 8/31/2014, electrical junction boxes and armored cable ran along and near the floor of a congested walk way were not protected from physical damage.
Recent events (2)
  • — I (S) $3750
  • — Z (S) $3750

View Biogen Idec, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339942906.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.