CAMBRIDGE, MA —
OSHA Inspection: BIOGEN IDEC, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BIOGEN IDEC, INC. in 14 CAMBRIDGE CENTER, CAMBRIDGE, MA 02142 (NAICS 325412). OSHA activity number 339942906.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BIOGEN IDEC, INC.
- Site address
- 14 CAMBRIDGE CENTER
- City
- CAMBRIDGE
- State
- MA
- ZIP
- 02142
- Mailing
- 14 CAMBRIDGE CENTER, CAMBRIDGE, MA 02142
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325412
- Employees
- 4000
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 B02
- Issued
- Sep 22, 2014
- Abate by
- Oct 25, 2014
- Penalty
- Initial $3,750 · Current $3,750
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Location - 14 Cambridge Center, Cambridge, MA (Interstitial Space): On or about 8/31/2014, armored cable was not secured and supported at interval in accordance with its listing and labeling (Ref. NFPA 70 Article 320). (b) Location - 14 Cambridge Center, Cambridge, MA (Interstitial Space): On or about 8/31/2014, an electrical junction box was not mounted in accordance with its listing and labeling (Ref. NFPA 70 Article 314).
Recent events (2)
- — I (S) $3750
- — Z (S) $3750
1910.303 G02 II
- Issued
- Sep 22, 2014
- Abate by
- Oct 25, 2014
- Penalty
- Initial $3,750 · Current $3,750
General-duty citation text
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage: (a) Location - 14 Cambridge Center, Cambridge, MA (Interstitial Space): On or about 8/31/2014, electrical junction boxes and armored cable ran along and near the floor of a congested walk way were not protected from physical damage.
Recent events (2)
- — I (S) $3750
- — Z (S) $3750
More inspections at Biogen Idec, INC.
View Biogen Idec, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 325412)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339942906.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.