FRANKLIN, WI —
OSHA Inspection: VENTURE ELECTRICAL CONTRACTORS, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of VENTURE ELECTRICAL CONTRACTORS, INC. in 8222 S. 51ST. ST., FRANKLIN, WI 53132 (NAICS 238210). OSHA activity number 339945362.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VENTURE ELECTRICAL CONTRACTORS, INC.
- Site address
- 8222 S. 51ST. ST.
- City
- FRANKLIN
- State
- WI
- ZIP
- 53132
- Mailing
- 2110 PEWAUKEE RD. SUITE 110, WAUKESHA, WI 53188
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 110
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.21 B02
- Issued
- Jan 29, 2015
- Abate by
- Mar 18, 2015
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury: (a) The employer failed to train an employee on electrical safe work practices. This exposed the employee to an electrical shock hazard.
Recent events (3)
- — F (S) $0
- — C (S) $6300
- — Z (S) $6300
1926.416 A01
- Issued
- Jan 29, 2015
- Abate by
- Feb 4, 2015
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: (a) An employee was working on a live electrical circuit which was not de-energized or guarded to prevent accidental contact of live parts.
Recent events (3)
- — F (S) $0
- — C (S) $6300
- — Z (S) $6300
1926.416 A03
- Issued
- Jan 29, 2015
- Abate by
- Feb 4, 2015
- Penalty
- Initial $6,300 · Current $1,500 Reduced
General-duty citation text
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into pysical or electrical contact with the electric power circuit. (a) The employer did not advise an employee of the location, energized state, the potential hazards associated with the electrical circuit, and the protective measures to be taken when working on the electrical power circuit. This exposed an employee to an electrical shock hazard.
Recent events (3)
- — F (O) $1500
- — C (S) $6300
- — Z (S) $6300
1926.417 A
- Issued
- Jan 29, 2015
- Abate by
- Feb 4, 2015
- Penalty
- Initial $6,300 · Current $1,500 Reduced
General-duty citation text
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged: (a) Employees were working on an energized circuit that was not locked/tagged out. This exposed an employee to an electrical shock hazard.
Recent events (3)
- — F (O) $1500
- — C (S) $6300
- — Z (S) $6300
1926.403 H
- Issued
- Jan 29, 2015
- Abate by
- Feb 4, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident: (a) Branch circuits were not legibly marked at electrical panel boxes to indicate their purpose.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Venture Electrical Contractors, INC.
View Venture Electrical Contractors, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339945362.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.