Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NESTLE WATERS

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of NESTLE WATERS in 11700 E. 47TH AVE, DENVER, CO 80239 (NAICS 312112). OSHA activity number 339952517.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nestle Waters — free Get an email when a new federal OSHA severe-injury report for Nestle Waters is published. One employer, no account, unsubscribe in one click.
Establishment
NESTLE WATERS
Site address
11700 E. 47TH AVE
City
DENVER
State
CO
ZIP
80239
Mailing
11700 E. 47TH AVE, DENVER, CO 80239
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
312112
Employees
55
Ownership type
A

4 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 5 1 instance 5 exposed
Issued
Feb 6, 2015
Abate by
Feb 26, 2015
Penalty
Initial $4,000 · Current $4,000
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:   (a)    Nestle Waters at 11700 E. 147th Ave. Denver, CO 80239: On and before 9/5/14, the employer did not ensure employees utilized the written Lockout/Tagout (LOTO) procedures developed by the company for the control of hazardous energy. Specifically, the employer did not ensure that LOTO procedures are followed during maintenance on the Sidel Blowmolder. This equipment is powered by multiple energy sources to include electrical and pneumatic.  This condition exposed employees to hazards associated with the sudden release of stored energy.  Abatement Note:  Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (1)
  • — Z (S) $4000

1910.147 C06 I

Serious Gravity 5 1 instance 5 exposed
Issued
Feb 6, 2015
Abate by
Feb 26, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i): The employer shall conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed.   (a)    Nestle Waters at 11700 E. 147th Ave. Denver, CO 80239: On and before 9/5/14, the employer did not conduct a periodic inspection of the energy control procedures for the control of hazardous energy.  Documents provided by the company indicate that the Lockout/Tagout (LOTO) Safety Policy and Guidelines have not been updated since October of 2011 and the specific written procedures for equipment such as but not limited to; the Sidel Blowmolder have not been reviewed since 2007.  This condition exposed employees to hazards associated with the sudden release of stored energy.  Abatement Note:  Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 5 exposed
Issued
Feb 6, 2015
Abate by
Feb 26, 2015
Penalty
Initial $2,550 · Current $2,550
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  (a)   Nestle Waters at 11700 E. 147th Ave. Denver, CO 80239: On and before 9/5/14, the employer did not ensure that flexible cords and/or cables were prevented from being used as a substitute for the fixed wiring of a structure in that a flexible electrical cord was used for providing power to a palletizer in the repacking area. This condition exposed employees to the hazard of electrical shock.   Abatement Note:  Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (1)
  • — Z (S) $2550

1910.305 B01 II

Serious Gravity 1 1 instance 5 exposed
Issued
Feb 6, 2015
Abate by
Feb 26, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.   (a) Nestle Waters at 11700 E. 147th Ave. Denver, CO 80239: On and before 9/5/14, the employer did not ensure that unused openings in the electrical panels were effectively closed. Numerous electrical panels had missing breakers which had not been closed. This condition exposed employees to the hazard of electrical shock.   Abatement Note:  Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (1)
  • — Z (S) $0

View Nestle Waters's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339952517.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.