OSHA Inspection: DATA MAIL, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DATA MAIL, INC. in 880 MARSHALL PHELPS ROAD, WINDSOR, CT 06095 (NAICS 541860). OSHA activity number 339986929.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Data Mail, INC. for free Get an email when a new federal OSHA severe-injury report for Data Mail, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
DATA MAIL, INC.
Site address
880 MARSHALL PHELPS ROAD
City
WINDSOR
State
CT
ZIP
06095
Mailing
240 HARTFORD AVENUE, NEWINGTON, CT 06111
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541860
Employees
402
Ownership type
Private (A)

2 citations on file for this inspection.

1910.303 G01 I

Serious Gravity 5 1 instance 400 exposed
Issued
Oct 10, 2014
Abate by
Dec 1, 2014
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1:  A.  On or about October 9, 2014, Roll Storage Area:  The working space before 120/208V electrical panels, identified as LXYZ, L1BI, L1A4A, L1A4 Sec 2, L1A4 Sec 1 and Blower Relay Panel was less than 36 inches by the placement of 6"x6" wooden barriers, 27 inches from the face of the panels.
Recent events (2)
  • · I (S) $1700
  • · Z (S) $3400

1910.303 G01 II

Serious Gravity 5 1 instance 400 exposed
Issued
Oct 10, 2014
Abate by
Dec 1, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  A.  On or about October 9, 2014, near Roll Staging Area:  The working space before 120/208V electrical panels, identified as LXYZ, L1BI, L1A4A, L1A4 Sec 2, L1A4 Sec 1 and Blower Relay Panel, was used for the storage of waste barrels and push brooms.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

View Data Mail, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339986929.