Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ACE BEGONIAS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ACE BEGONIAS, INC. in 231 SEYMOUR RD, WOODBRIDGE, CT 06525 (NAICS 111421). OSHA activity number 340008713.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ACE Begonias, INC. — free Get an email when a new federal OSHA severe-injury report for ACE Begonias, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
ACE BEGONIAS, INC.
Site address
231 SEYMOUR RD
City
WOODBRIDGE
State
CT
ZIP
06525
Mailing
231 SEYMOUR RD, WOODBRIDGE, CT 06525
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
111421
Employees
16
Ownership type
A

9 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 5 3 instances 5 exposed
Issued
Dec 23, 2014
Abate by
Jan 21, 2015
Penalty
Initial $2,000 · Current $1,400 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i).    Worksite:  The electrical distribution panels were missing circuit breakers and exposed to live parts, and the employees working around the panels were not adequately protected from the electrical shock hazards.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2000

1910.305 B02

Serious Gravity 10 6 instances 5 exposed
Issued
Dec 23, 2014
Abate by
Jan 21, 2015
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.    Establishment:  The junction/pull boxes installed in the main growing area, boiler area and around coal furnaces were not provided with appropriate covers, and the internal wirings were exposed.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.305 E01

Serious Gravity 10 1 instance 5 exposed
Issued
Dec 23, 2014
Abate by
Jan 21, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures.  Establishment: The electrical raceways and enclosures, installed in damp and wet locations were neither weatherproof types nor installed appropriately to prevent water from entering boxes.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 X

Serious Gravity 5 3 instances 5 exposed
Issued
Dec 23, 2014
Abate by
Feb 11, 2015
Penalty
Initial $1,600 · Current $1,120 Reduced
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points.    Establishment: The extension and flexible cords, used as permanent wiring were not protected from accidental damages by sharp corners.
Recent events (2)
  • — I (S) $1120
  • — Z (S) $1600

1910.305 G01 IV A

Serious Gravity 5 5 instances 5 exposed
Issued
Dec 23, 2014
Abate by
Feb 11, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  Establishment: The extension and flexible cords, used to supply power to the equipment, such as (but not limited to) coal burning furnaces, pumps and motors for fertilizer mixers were used as a substitute for permanent wiring.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B02

Other-than-serious 3 instances 5 exposed
Issued
Dec 23, 2014
Abate by
Jan 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit".  Establishment:  The exits were not marked by a sign reading Exit.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B02

Other-than-serious 1 instance 1 exposed
Issued
Dec 23, 2014
Abate by
Jan 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  Establishment: The employer did not ensure that all electric outlet boxes were provided with covers.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 B07 I

Other-than-serious 1 instance 1 exposed
Issued
Dec 23, 2014
Abate by
Jan 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.  Establishment: Unused openings in electrical distribution panels were not effectively closed.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 3 instances 1 exposed
Issued
Dec 23, 2014
Abate by
Feb 11, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.  Establishment: The employer did not ensure that electrical distribution panels were marked to indicate the purpose of each branch circuit.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View ACE Begonias, INC.'s full OSHA safety record →