WOOD RIVER, IL ·
OSHA Inspection: GBW RAILCAR SERVICES, L.L.C.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of GBW RAILCAR SERVICES, L.L.C. in 435 OLD ST. LOUIS ROAD, WOOD RIVER, IL 62095 (NAICS 488210). OSHA activity number 340044874.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GBW RAILCAR SERVICES, L.L.C.
- Site address
- 435 OLD ST. LOUIS ROAD
- City
- WOOD RIVER
- State
- IL
- ZIP
- 62095
- Mailing
- 435 OLD ST. LOUIS ROAD, WOOD RIVER, IL 62095
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 488210
- Employees
- 120
- Ownership type
- Private (A)
Citations
7 citations on file for this inspection.
1910.303 B02
- Issued
- Feb 20, 2015
- Penalty
- Initial $2,700 · Current $1,890 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) In the Inspection/Supervisor Office, south section, the 110 volt electrical Relocatable Power Taps were series-connected to other RPTs.
Recent events (2)
- · I (S) $1890
- · Z (S) $2700
1910.303 B07 IV
- Issued
- Feb 20, 2015
- Penalty
- Initial $2,700 · Current $1,890 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): 29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: In the Tool Room, on the east wall, the 110 volt electrical receptacle had been damaged and had burn marks were present indicating overcurrent damage.
Recent events (2)
- · I (S) $1890
- · Z (S) $2700
1910.303 G02 I
- Issued
- Feb 20, 2015
- Penalty
- Initial $2,700 · Current $1,890 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) In the Dome Shop, near track 25, the 110 volt electrical panel breaker box, the block wall below had been damaged and the electrical wiring was exposed. b) In the Inspection/Supervisor Office, south section, a 110 volt electrical receptacle was pulled out away from the wall.
Recent events (2)
- · I (S) $1890
- · Z (S) $2700
1910.304 G05
- Issued
- Feb 20, 2015
- Abate by
- Mar 18, 2015
- Penalty
- Initial $2,700 · Current $1,890 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) In the Inspection/Supervisor Office, south end, on the 110 volt electrical Relocatable Power Tap, the ground circuit was not complete. b) In the Inspection/Supervisors Office, north end, on the 110 volt electrical receptacle that was part of the light switch, the ground circuit was not complete. c) In the Tool Room, east wall, on the 110 volt electrical receptacle, the ground circuit was not complete.
Recent events (2)
- · I (S) $1890
- · Z (S) $2700
1910.305 B01 I
- Issued
- Feb 20, 2015
- Penalty
- Initial $3,600 · Current $2,520 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: a) Outside Area, by the Lift Station, on the 480 volt electrical panel, the conduit that contained the electrical wiring was separated from breaker box, allowing strain to be placed upon the wiring that can cause abrasions in the insulation. b) In the Blast Bag House, the 230/460 volt motor on the dust collector, the conduit which contained the electrical wiring was separated from the motor box, allowing strain to be placed upon the wiring that can cause abrasions in the insulation.
Recent events (2)
- · I (S) $2520
- · Z (S) $3600
1910.305 G01 IV C
- Issued
- Feb 20, 2015
- Penalty
- Initial $2,700 · Current $1,890 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were run through doorways, windows or floors: a) Air Shop near Track 7, a 110 volt electrical flexible cord was run through a window to supply electrical power to outside equipment.
Recent events (2)
- · I (S) $1890
- · Z (S) $2700
1910.22 C
- Issued
- Feb 20, 2015
- Abate by
- Mar 18, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(c): Covers and/or guardrails were not provided to protect personnel from the hazards of open pits, tanks, vats, ditches, impalement hazards, etc.: a) Track 7, at the Fire Hydrant, the metal bar cage installed to protect the hydrant had sharp angle iron protruding up that poses a hazard for employees who could fall onto the cage.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at GBW Railcar Services, L.L.C.
View GBW Railcar Services, L.L.C.'s full OSHA safety record →
More inspections in this industry (NAICS 488210)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 340044874.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.