OSHA Inspection: HARLAN ELECTRIC COMPANY INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of HARLAN ELECTRIC COMPANY INC. in 6533 INTERCHANGE RD., LEHIGHTON, PA 18235 (NAICS 221122). OSHA activity number 340045673.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Harlan Electric Company INC. — free Get an email when a new federal OSHA severe-injury report for Harlan Electric Company INC. is published. One employer, no account, unsubscribe in one click.
Site address
6533 INTERCHANGE RD.
City
LEHIGHTON
State
PA
ZIP
18235
Mailing
1213 PAXTON CHURCH RD., HARRISBURG, PA 17110
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
10
Ownership type
A

4 citations on file for this inspection.

1926.962 B

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 24, 2015
Abate by
Jun 11, 2015
Penalty
Initial $7,000 · Current $7,000
29 CFR 1926.962(b): For any employee working transmission and distribution lines or equipment as deenergized, the employer did not ensure that the lines or equipment were deenergized under the provisions of 1926.961 and did not ensure proper grounding of the lines or equipment as specified in paragraphs (c) through (h) of this section.  a) 6533 Interchange Rd., Lehighton, PA: On or about October 27, 2014, employees were in the process of installing lightning arrestors on a 69KV power line where the hazard of induced voltage was present from energized 500KV and 69KV power lines in close proximity and the line was not deenergized and temporary protective grounds were not installed, resulting in the electrocution of an employee.   Abatement Certification and Documentation Required.
Recent events (3)
  • — F (S) $7000
  • — C (S) $7000
  • — Z (S) $7000

1926.950 D01 IV

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Apr 24, 2015
Abate by
Jun 11, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.961(c)(7): The employer did not ensure the installation of protective grounds as required by � 1926.962:  a) 6533 Interchange Rd., Lehighton, PA: On or about October 27, 2014, employees were in the process of installing lightning arrestors on a 69KV power line in close proximity to energized 500KV and 69KV power lines and protective grounds were not installed, resulting in the electrocution of an employee.   Abatement Certification and Documentation Required.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1926.950 D01 III

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Apr 24, 2015
Abate by
Jun 11, 2015
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1926.961(c)(6): The employer did not ensure that the lines and equipment were deenergized by testing the lines and equipment to be worked with a device designed to detect voltage:  a) 6533 Interchange Rd., Lehighton, PA: On or about October 27, 2014, employees were in the process of installing lightning arrestors on a 69KV power line and the line was not tested to confirm it was deenergized, exposing the employees to an electrocution hazard.   Abatement Certification and Documentation Required.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1926.960 C01 III A

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Apr 24, 2015
Abate by
Jun 11, 2015
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1926.960(c)(1)(iii)(A):  The employer did not ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance unless the employee is insulated from the energized part (rubber insulating gloves and sleeves worn in accordance with paragraph (c)(2) of this section constitutes insulation):  a) 6533 Interchange Rd., Lehighton, PA: On or about October 27, 2014, the employer failed to ensure employees in the process of installing lightning arrestors on an energized 69KV power line were using personal protective equipment (PPE), including rubber insulating gloves and sleeves, exposing them to an electrocution hazard.  Abatement Certification and Documentation Required.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000