Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DEFIANCE ELECTRIC, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DEFIANCE ELECTRIC, LLC in 1 AIRPORT ROAD, MANCHESTER, NH 03101 (NAICS 238210). OSHA activity number 340053073.

Watch Defiance Electric, LLC — free Get an email when a new federal OSHA severe-injury report for Defiance Electric, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1 AIRPORT ROAD
City
MANCHESTER
State
NH
ZIP
03101
Mailing
86 CHOSEN VALE LANE, SUITE 202, ENFIELD, NH 03748
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

4 citations on file for this inspection.

1926.21 B02

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury:    a. Site- Employees exposed to electric shock and arc flash hazards were not provided with safe electrical work practice training including lock out/tag out procedures, required personal protective equipment, and voltage testing procedures from the employer. On or about October 27, 2014 a temporary employee who was not provided with safe electrical work practice training sustained an electric shock and fell off of a step ladder when they contacted live power operating at 277 volts.
Recent events (2)
  • — I (S) $2800
  • — Z (S) $2800

1926.416 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $0.00 Reduced
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:    a. Site- An employee was not protected from electric shock where a lighting circuit that was being worked on was not de-energized and locked out. On or about October 27, 2014 a temporary employee who was working on a live lighting circuit sustained an electric shock and fell off of a step ladder when they contacted live power operating at 277 volts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2800

1926.417 B

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $0.00 Reduced
29 CFR 1926.417(b): Equipment or circuits that were de-energized were not rendered inoperative:    a. Site- Employees replacing light fixtures were not protected from electric shock and burns where the employer did not implement energy control procedures that included rendering de-energized electric circuits that are to be worked on inoperative.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2800

1926.417 C

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.417(c): Tags were not placed to identify plainly the equipment or circuits being worked on:    a. Site- Employees replacing light fixtures were not protected from electric shock and burns where the employer did not implement energy control procedures that included placing tags on circuit breakers that control de-energized electric circuits that are to be worked on.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340053073.