TRAINER, PA —
OSHA Inspection: MONROE ENERGY, LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of MONROE ENERGY, LLC in 4101 POST ROAD, TRAINER, PA 19061 (NAICS 324110). OSHA activity number 340053982.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MONROE ENERGY, LLC
- Site address
- 4101 POST ROAD
- City
- TRAINER
- State
- PA
- ZIP
- 19061
- Mailing
- 4101 POST ROAD, TRAINER, PA 19061
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 468
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.119 F03
- Issued
- Apr 24, 2015
- Abate by
- May 13, 2015
- Penalty
- Initial $2,805 · Current $2,805
General-duty citation text
29 CFR 1910.119(f)(3): The operating procedures were not reviewed as often as necessary to assure that they reflect current operating practice, including changes that result from changes in process chemicals, technology, and equipment, and changes to facilities: a. Area One, Platformer Heater - The employer did not clearly state whether the written Critical Instrument Test Procedure Number RG/CIXSD13603KV entitled: "Platformer #2 Reheater (13-H-3) Emergency Fuel Gas Shut-off System (XSD-13603) No Testing of High/Low Pressure Transmitters" was for the quick test or for the long test. On or About October 31, 2014 b. Area Two, VGO Heater -The employer did not ensure that written Critical Instrument Test Procedure Number RG/CIXD32600KV entitled: "VGO Heater Emergency Fuel Gas Shut-off System, (XSD-32600) (No Testing of Low Flow or Low/High Pressure Transmitters)" was updated to reflect that the employer had converted VGO Heater (Vacuum Gas-Oil Heater) from gas-oil service to diesel service. On or About October 31, 2014
Recent events (1)
- — Z (S) $2805
More inspections at Monroe Energy, LLC
View Monroe Energy, LLC's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340053982.