JERSEY CITY, NJ ·
OSHA Inspection: ISS FACILITY SERVICES INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ISS FACILITY SERVICES INC. in LIBERTY STATE PARK 222 JERSEY CITY BLVD, JERSEY CITY, NJ 07305 (NAICS 238210). OSHA activity number 340059393.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ISS FACILITY SERVICES INC.
- Site address
- LIBERTY STATE PARK 222 JERSEY CITY BLVD
- City
- JERSEY CITY
- State
- NJ
- ZIP
- 07305
- Mailing
- 81 DORSA AVE, LIVINGSTON, NJ 07039
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 8
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.333 A01
- Issued
- Apr 15, 2015
- Abate by
- May 8, 2015
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs. a) 222 Jersey City Blvd Jersey City, NJ (Mechanical Room) Employees removed fuses from the mcc panel without deenergizing the panel, exposing employees to electrical hazards. Violation occurred on or about 11/03/2014
Recent events (3)
- · F (S) $0
- · C (S) $7000
- · Z (S) $7000
1910.333 A02
- Issued
- Apr 15, 2015
- Abate by
- May 8, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved. a) 222 Jersey City Blvd Jersey City, NJ (Mechanical Room) Employees were exposed to shocks, fire and arc flashtblast hazards when working on energized electrical equipment without using electrical safety related practices such as: proper personal protective equipment, fire resistant clothing and voltage rated tools. Violation occurred on or about 11/03/2014
Recent events (3)
- · F (S) $0
- · C (S) $0
- · Z (S) $0
1910.335 A01 I
- Issued
- Apr 15, 2015
- Abate by
- May 8, 2015
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed. a) 222 Jersey City Blvd Jersey City, NJ (Mechanical Room) An employee was changing a fuse on an energized bucket at 480 Volts and was exposed to shock and flash hazard without the use of arc rated clothing. Violation occurred on or about 11/03/2014
Recent events (3)
- · F (S) $0
- · C (S) $7000
- · Z (S) $7000
1910.335 A02 I A
- Issued
- Apr 15, 2015
- Abate by
- May 8, 2015
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(2)(i)(A): Fuse handling equipment, insulated for the circuit voltage, shall be used to remove or install fuses when the fuse terminals are energized. a) 222 Jersey City Blvd Jersey City, NJ (Mechanical Room) Fuse handling equipment, insulated for the circuit voltage, was not used to remove or install fuses when the fuse terminals were energized. Violation occurred on or about 11/03/2014
Recent events (3)
- · F (S) $0
- · C (S) $7000
- · Z (S) $7000
More inspections at ISS Facility Services INC.
View ISS Facility Services INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 340059393.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.