Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: HANBY FARMS INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of HANBY FARMS INC. in 10790 NEWARK ROAD, NASHPORT, OH 43830 (NAICS 424510). OSHA activity number 340067347.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hanby Farms INC. for free Get an email when a new federal OSHA severe-injury report for Hanby Farms INC. is published. One employer, no account, unsubscribe in one click.
Establishment
HANBY FARMS INC.
Site address
10790 NEWARK ROAD
City
NASHPORT
State
OH
ZIP
43830
Mailing
P.O. BOX 97, NASHPORT, OH 43830
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
47
Ownership type
Private (A)

5 citations on file for this inspection.

1910.272 J01

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 29, 2015
Abate by
Jun 3, 2015
Penalty
Initial $3,500 · Current $1,925 Reduced

Hazardous substances E200M102M104

29 CFR 1910.272(j)(1): Housekeeping. The employer shall develop and implement a written housekeeping program that establishes the frequency and method(s) determined best to reduce accumulations of fugitive grain dust on ledges, floors, equipment, and other exposed surfaces.  On or about November 6, 2014, the employer had not adequately developed and then implemented a housekeeping program. The employer's written program did not establish the frequency and the methods to reduce accumulations of combustible grain dust in that it did not establish:    a. Cleaning frequency and specific schedule for reducing accumulations of grain dust on ledges, floors, equipment, other exposed surfaces and for priority housekeeping areas. b. Methods used to remove grain dust and spills such as the use of non-sparking tools, brooms, brushes, use of compressed air (with equipment turned off as required by (j)(3)) and Class II rated vacuums.  c. Methods for the disposal of grain dust.
Recent events (2)
  • · I (S) $1925
  • · Z (S) $3500

1910.305 B02 I

Serious Gravity 5 2 instances 6 exposed
Issued
Apr 29, 2015
Abate by
May 11, 2015
Penalty
Initial $3,500 · Current $1,925 Reduced

Hazardous substances 8870E200

29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear.  a. On or about November 6, 2014, a pull box mounted on top of the electrical room in the Mill Feed building did not have the dust tight cover installed, or replaced following removal. This equipment is an ignition source for potential combustible grain dust fire and/or explosion in this hazardous location.   b. In the Old Set up Drymor room, the box located on the south wall had exposed live parts of 50 VAC or greater. Employees were exposed to an electrical contact hazard.
Recent events (2)
  • · I (S) $1925
  • · Z (S) $3500

1910.307 C

Serious Gravity 10 6 instances 6 exposed
Issued
Apr 29, 2015
Abate by
Jun 3, 2015
Penalty
Initial $4,900 · Current $2,695 Reduced

Hazardous substances E200M102M104

29 CFR 1910.307(c): Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location.    On or about November 6, 2014, electrical equipment was not appropriate for the hazardous location(s) in the feed mill, such as but not limited to: a. the rectangular junction box/pull box mounted on the wall outside the control room near the pellet machine is not dust tight, b. a light fixture mounted on structural steel that is missing a component (cover) which allows direct contact with grain dust onto the light bulb, and   c. in the feed mill electrical room, electrical equipment including panels, boxes, a transformer and disconnects. Additionally a disconnect box was wired improperly and multiple control panels had removed covers/housings in this same location with open air access to live electrical components.
Recent events (2)
  • · I (S) $2695
  • · Z (S) $4900

1910.134 C02 I

Other-than-serious 1 instance 6 exposed
Issued
Apr 29, 2015
Abate by
Jun 3, 2015
Penalty
Initial $0 · Current $0

Hazardous substances G109R103

29 CFR 1910.134(c)(2)(i): An employer may provide respirators at the request of employees or permit employees to use their own respirators, if the employer determines that such respirator use will not in itself create a hazard. If the employer determines that any voluntary respirator use is permissible, the employer shall provide the respirator users with the information contained in Appendix D to this section ("Information for Employees Using Respirators When Not Required Under the Standard"); and   a. On or about November 6, 2014, the employer had failed to provide Appendix D for employees as part of a respiratory protection program with voluntary respirator use only.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.272 M03

Other-than-serious 1 instance 6 exposed
Issued
Apr 29, 2015
Abate by
Jun 3, 2015
Penalty
Initial $0 · Current $0

Hazardous substances E200M102M104

29 CFR 1910.272(m)(3): Preventive maintenance. A certification record shall be maintained of each inspection, performed in accordance with this paragraph (m), containing the date of the inspection, the name of the person who performed the inspection and the serial number, or other identifier, of the equipment specified in paragraph (m)(1)(i) of this section that was inspected.  a. On or about November 6, 2014, the employer failed to assure that certification of preventive maintenance records was performed and that the records are maintained for equipment covered by this part.