NASHPORT, OH ·
OSHA Inspection: HANBY FARMS INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of HANBY FARMS INC. in 10790 NEWARK ROAD, NASHPORT, OH 43830 (NAICS 424510). OSHA activity number 340067347.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HANBY FARMS INC.
- Site address
- 10790 NEWARK ROAD
- City
- NASHPORT
- State
- OH
- ZIP
- 43830
- Mailing
- P.O. BOX 97, NASHPORT, OH 43830
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424510
- Employees
- 47
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.272 J01
- Issued
- Apr 29, 2015
- Abate by
- Jun 3, 2015
- Penalty
- Initial $3,500 · Current $1,925 Reduced
E200M102M104
General-duty citation text
29 CFR 1910.272(j)(1): Housekeeping. The employer shall develop and implement a written housekeeping program that establishes the frequency and method(s) determined best to reduce accumulations of fugitive grain dust on ledges, floors, equipment, and other exposed surfaces. On or about November 6, 2014, the employer had not adequately developed and then implemented a housekeeping program. The employer's written program did not establish the frequency and the methods to reduce accumulations of combustible grain dust in that it did not establish: a. Cleaning frequency and specific schedule for reducing accumulations of grain dust on ledges, floors, equipment, other exposed surfaces and for priority housekeeping areas. b. Methods used to remove grain dust and spills such as the use of non-sparking tools, brooms, brushes, use of compressed air (with equipment turned off as required by (j)(3)) and Class II rated vacuums. c. Methods for the disposal of grain dust.
Recent events (2)
- · I (S) $1925
- · Z (S) $3500
1910.305 B02 I
- Issued
- Apr 29, 2015
- Abate by
- May 11, 2015
- Penalty
- Initial $3,500 · Current $1,925 Reduced
8870E200
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. a. On or about November 6, 2014, a pull box mounted on top of the electrical room in the Mill Feed building did not have the dust tight cover installed, or replaced following removal. This equipment is an ignition source for potential combustible grain dust fire and/or explosion in this hazardous location. b. In the Old Set up Drymor room, the box located on the south wall had exposed live parts of 50 VAC or greater. Employees were exposed to an electrical contact hazard.
Recent events (2)
- · I (S) $1925
- · Z (S) $3500
1910.307 C
- Issued
- Apr 29, 2015
- Abate by
- Jun 3, 2015
- Penalty
- Initial $4,900 · Current $2,695 Reduced
E200M102M104
General-duty citation text
29 CFR 1910.307(c): Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. On or about November 6, 2014, electrical equipment was not appropriate for the hazardous location(s) in the feed mill, such as but not limited to: a. the rectangular junction box/pull box mounted on the wall outside the control room near the pellet machine is not dust tight, b. a light fixture mounted on structural steel that is missing a component (cover) which allows direct contact with grain dust onto the light bulb, and c. in the feed mill electrical room, electrical equipment including panels, boxes, a transformer and disconnects. Additionally a disconnect box was wired improperly and multiple control panels had removed covers/housings in this same location with open air access to live electrical components.
Recent events (2)
- · I (S) $2695
- · Z (S) $4900
1910.134 C02 I
- Issued
- Apr 29, 2015
- Abate by
- Jun 3, 2015
- Penalty
- Initial $0 · Current $0
G109R103
General-duty citation text
29 CFR 1910.134(c)(2)(i): An employer may provide respirators at the request of employees or permit employees to use their own respirators, if the employer determines that such respirator use will not in itself create a hazard. If the employer determines that any voluntary respirator use is permissible, the employer shall provide the respirator users with the information contained in Appendix D to this section ("Information for Employees Using Respirators When Not Required Under the Standard"); and a. On or about November 6, 2014, the employer had failed to provide Appendix D for employees as part of a respiratory protection program with voluntary respirator use only.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.272 M03
- Issued
- Apr 29, 2015
- Abate by
- Jun 3, 2015
- Penalty
- Initial $0 · Current $0
E200M102M104
General-duty citation text
29 CFR 1910.272(m)(3): Preventive maintenance. A certification record shall be maintained of each inspection, performed in accordance with this paragraph (m), containing the date of the inspection, the name of the person who performed the inspection and the serial number, or other identifier, of the equipment specified in paragraph (m)(1)(i) of this section that was inspected. a. On or about November 6, 2014, the employer failed to assure that certification of preventive maintenance records was performed and that the records are maintained for equipment covered by this part.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at Hanby Farms INC.