Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SCHIER PRODUCTS COMPANY

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of SCHIER PRODUCTS COMPANY in 9500 WOODEND RD, KANSAS CITY, KS 66111 (NAICS 327332). OSHA activity number 340080258.

Watch Schier Products Company — free Get an email when a new federal OSHA severe-injury report for Schier Products Company is published. One employer, no account, unsubscribe in one click.
Site address
9500 WOODEND RD
City
KANSAS CITY
State
KS
ZIP
66111
Mailing
9500 WOODEND RD, KANSAS CITY, KS 66111
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327332
Employees
40
Ownership type
A

3 citations on file for this inspection.

1910.303 A

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1400.00 Reduced
29 CFR 1910.303(a): The conductors and/or equipment required or permitted by this subpart were not approved:  Employees were exposed to a 110 VAC electrical shock hazard.  The remote on/off switch taped to the inlet hose of the wall mounted vacuum was job made and was not listed, labeled, or approved by a nationally recognized testing laboratory or the equipment manufacturer.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1400.00 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  Employees were exposed to a 110 VAC electrical shock hazard.  The live conductors providing power to the job made, remote on/off switch on the wall mounted vacuum inlet hose were not protected from employee contact.   29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1910.305 G01 IV A

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1400.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Employees were exposed to 110 VAC electrical shock hazard.  The wall mounted vacuum at the LB table was provided power through 2 extension cords.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800