CHICOPEE, MA —
OSHA Inspection: THE PORTER AND CHESTER INSTITUTE, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of THE PORTER AND CHESTER INSTITUTE, INC. in 1984 WESTOVER ROAD, CHICOPEE, MA 01022 (NAICS 611519). OSHA activity number 340081546.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE PORTER AND CHESTER INSTITUTE, INC.
- Site address
- 1984 WESTOVER ROAD
- City
- CHICOPEE
- State
- MA
- ZIP
- 01022
- Mailing
- 134 DULONG CIRCLE, CHICOPEE, MA 01022
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 611519
- Employees
- 45
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.132 D01
- Issued
- Jan 8, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $5,000 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): Electrical and HVACR labs, Porter and Chester Institute, 1984 Westover Road, Chicopee, Massachusetts; The employer did not perform a workplace assessment of the HVACR and electrical labs to determine the hazards present and which PPE to provide to employees to protect them from those hazards.
Recent events (2)
- — I (S) $2500
- — Z (S) $5000
1910.132 D02
- Issued
- Jan 8, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment: Electrical and HVACR labs, Porter and Chester Institute, 1984 Westover Road, Chicopee, Massachusetts; The employer did not certify in writing that a workplace assessment of the HVACR and electrical labs had been performed to determine the hazards present and which PPE to provide to employees.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Jan 8, 2015
- Abate by
- Jan 28, 2015
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Electrical and HVACR Labs, Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts; Electrical and HVACR instructors were not provided electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a. electrically rated gloves to protect them from electrical shock hazards when performing voltage testing on circuits greater than 50 VAC. b. uniform shirts provided by the employer for instructors are not arc rated and have a poly blend that could melt to employees or catch fire if exposed to an arc blast.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C06 I
- Issued
- Jan 8, 2015
- Abate by
- May 29, 2015
- Penalty
- Initial $5,000 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts; The employer did not conduct periodic inspections of the energy control procedures at least annually by an authorized employee to ensure that the procedures met the requirements of 29 CFR 1910.147 and were being followed for locking out equipment regularly locked out in the HVACR and electrical labs.
Recent events (2)
- — I (S) $2500
- — Z (S) $5000
1910.147 C07 I
- Issued
- Jan 8, 2015
- Abate by
- May 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices: Electrical and HVACR instructors, Porter and Chester Institute, 1984 Westover Road, Chicopee, Massachusetts; The employer did not provide lockout training to employees from the Electrical and HVACR areas to ensure they had acquired the knowledge and skills required for the safe application, usage, and removal of energy control devices.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Jan 8, 2015
- Abate by
- Mar 13, 2015
- Penalty
- Initial $3,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Electrical and HVACR Labs, Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts; Junction boxes in the electrical and HVAC labs had missing knockouts that were not effectively closed exposing employees to electric shock hazards.
Recent events (2)
- — I (S) $1500
- — Z (S) $3000
1910.176 B
- Issued
- Jan 8, 2015
- Abate by
- Jan 14, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.176(b): Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse: Electrical lab and HVAC lab, Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts; Ladders were not stacked, blocked, interlocked, or chained to prevent sliding or falling.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.333 B02 III E
- Issued
- Jan 8, 2015
- Abate by
- May 22, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(iii)(E): Locks were placed without tags, without meeting the conditions in 1910.333(b)(2)(iii)(E)(1) through 1910.333(b)(2)(iii)(E)(3): Electrical and HVACR Labs, Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts; Locks were hung on equipment in the HVACR and electrical labs without tags, without meeting the conditions required in exemption 1910.333(b)(2)(iii)(E)(2), which states that tags are not required if locks are not left on equipment for more than one shift.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at The Porter and Chester Institute, INC.
View The Porter and Chester Institute, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 611519)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340081546.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.