Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,473Inspections Most recent open 2026-07-28 Last loaded 2026-07-31

OSHA Inspection: THE PORTER AND CHESTER INSTITUTE, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of THE PORTER AND CHESTER INSTITUTE, INC. in 1984 WESTOVER ROAD, CHICOPEE, MA 01022 (NAICS 611519). OSHA activity number 340081546.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Porter and Chester Institute, INC. — free Get an email when a new federal OSHA severe-injury report for The Porter and Chester Institute, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1984 WESTOVER ROAD
City
CHICOPEE
State
MA
ZIP
01022
Mailing
134 DULONG CIRCLE, CHICOPEE, MA 01022
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
611519
Employees
45
Ownership type
A

8 citations on file for this inspection.

1910.132 D01

Serious Gravity 5 1 instance 7 exposed
Issued
Jan 8, 2015
Abate by
Jul 31, 2015
Penalty
Initial $5,000 · Current $2,500 Reduced
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE):  Electrical and HVACR labs, Porter and Chester Institute, 1984 Westover Road, Chicopee, Massachusetts;  The employer did not perform a workplace assessment of the HVACR and electrical labs to determine the hazards present and which PPE to provide to employees to protect them from those hazards.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $5000

1910.132 D02

Serious Gravity 1 1 instance 7 exposed
Issued
Jan 8, 2015
Abate by
Jul 31, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment:  Electrical and HVACR labs, Porter and Chester Institute, 1984 Westover Road, Chicopee, Massachusetts;  The employer did not certify in writing that a workplace assessment of the HVACR and electrical labs had been performed to determine the hazards present and which PPE to provide to employees.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 5 2 instances 7 exposed
Issued
Jan 8, 2015
Abate by
Jan 28, 2015
Penalty
Initial $0 · Current $0

Hazardous substances 8870

29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  Electrical and HVACR Labs, Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts; Electrical and HVACR instructors were not provided electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  a.  electrically rated gloves to protect them from electrical shock hazards when performing voltage testing on circuits greater than 50 VAC. b.  uniform shirts provided by the employer for instructors are not arc rated and have a poly blend that could melt to employees or catch fire if exposed to an arc blast.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C06 I

Serious Gravity 5 1 instance 7 exposed
Issued
Jan 8, 2015
Abate by
May 29, 2015
Penalty
Initial $5,000 · Current $2,500 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts;  The employer did not conduct periodic inspections of the energy control procedures at least annually by an authorized employee to ensure that the procedures met the requirements of 29 CFR 1910.147 and were being followed for locking out equipment regularly locked out in the HVACR and electrical labs.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $5000

1910.147 C07 I

Serious Gravity 1 1 instance 7 exposed
Issued
Jan 8, 2015
Abate by
May 29, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices:  Electrical and HVACR instructors, Porter and Chester Institute, 1984 Westover Road, Chicopee, Massachusetts;  The employer did not provide lockout training to employees from the Electrical and HVACR areas to ensure they had acquired the knowledge and skills required for the safe application, usage, and removal of energy control devices.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 1 instance 7 exposed
Issued
Jan 8, 2015
Abate by
Mar 13, 2015
Penalty
Initial $3,000 · Current $1,500 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   Electrical and HVACR Labs, Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts;  Junction boxes in the electrical and HVAC labs had missing knockouts that were not effectively closed exposing employees to electric shock hazards.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $3000

1910.176 B

Other-than-serious 1 instance 4 exposed
Issued
Jan 8, 2015
Abate by
Jan 14, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.176(b): Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse:  Electrical lab and HVAC lab, Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts; Ladders were not stacked, blocked, interlocked, or chained to prevent sliding or falling.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.333 B02 III E

Other-than-serious 1 instance 7 exposed
Issued
Jan 8, 2015
Abate by
May 22, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(iii)(E): Locks were placed without tags, without meeting the conditions in 1910.333(b)(2)(iii)(E)(1) through 1910.333(b)(2)(iii)(E)(3):  Electrical and HVACR Labs, Porter and Chester, 1984 Westover Road, Chicopee, Massachusetts; Locks were hung on equipment in the HVACR  and electrical labs without tags, without meeting the conditions required in exemption 1910.333(b)(2)(iii)(E)(2), which  states that tags are not required if locks are not left on equipment for more than one shift.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View The Porter and Chester Institute, INC.'s full OSHA safety record →