HAWTHORNE, NV —
OSHA Inspection: SOC NEVADA LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SOC NEVADA LLC in 2 SOUTH MAINE AVENUE, HAWTHORNE, NV 89415 (NAICS 423930). OSHA activity number 340082775.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SOC NEVADA LLC
- Site address
- 2 SOUTH MAINE AVENUE
- City
- HAWTHORNE
- State
- NV
- ZIP
- 89415
- Mailing
- 2 SOUTH MAINE AVENUE BUILDING 37, HAWTHORNE, NV 89415
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423930
- Employees
- 460
- Ownership type
- A
Citations
12 citations on file for this inspection.
1910.22 D01
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate. a) At Building 11, the mezzanine deck, used for storage by the wash room area, was not marked with the load limit.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.141 A03 I
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $4,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.141(a)(3)(i): Places of employment were not kept clean to the extent that the nature of the work allowed. a) At Building 117-6 second floor, numerous glass like particles of TNT crystals were allowed to grow and accumulate in the autoclave kettles.
Recent events (2)
- — I (O) $1000
- — Z (S) $4000
1910.147 C01
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative. a) At Hawthorne Army Depot the written energy control program did not include periodic inspection procedures and employee training.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
1910.147 C04 I
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $7,000 · Current $6,000 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section. a) At Hawthorne Army Depot the written energy control program procedures did not include specific for equipment such as but not limited to Building 63 elevator, cranes and chlorine systems.
Recent events (2)
- — I (S) $6000
- — Z (S) $7000
1910.147 C05 II B
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $7,000 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.147(c)(5)(ii)(B): Lockout and tag-out devices were not standardized within the facility in at least one of the following criteria: color; shape; or size. a. In Building 63, the lockout/tag-out (LO/TO) station locks were color coded red and the lock used on the cargo elevator switch was a master brand padlock. b. In Building 10, the lockout/tag-out (LO/TO) station locks were color coded red and in numerical sequence, the lock used for the Square D switch for the grinder was a small master lock with an "out of service" tag and the lock in use for the General Electric Main Switch was a long stem Ace brand padlock. c. In Building 95 electric shop, there were no locks in the lockout/tag-out (LO/TO) station and the lock in use on the Square D switch next to the office refrigerator was a master lock. d. In Building 63 and 95, the tag in use for the cargo elevator said "Do not start" with solid red color and other tags including the electrical shop tags were the standard white with red stripes that said "Do not operate". e. In Building 63, the "do not start" red tag on the cargo elevator switch was dated 2-9-11 and but did not identify the name of the person who applied the tag and a phone contact number.
Recent events (2)
- — I (S) $5000
- — Z (S) $7000
1910.147 C06 I
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: a) At Hawthorne Army Depot Lockout-Tag-out Procedures BOP.IOP.MUO.0208 was not followed, there were no evidence that periodic and/or inspections were conducted. b) In Building 63, the lockout/tag-out (LO/TO) station locks were color coded red, the lock used on the cargo elevator switch was a master brand padlock, the tag on the cargo elevator switch was dated 2-9-11.
Recent events (2)
- — I (S) $3500
- — Z (S) $7000
1910.147 C09
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(9): Affected employees were not notified by the employer or authorized employee of the application and removal of lockout devices or tag-out devices: a. In Building 95, Electric shop, affected employees including the supervisor did not know when locks/tags were applied and removed nor was there accountability on when and what kind of locks and tags would be used.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
1910.244 A01 II
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $4,000 · Current $4,000
General-duty citation text
29 CFR 1910.244(a)(1)(ii): Rated load(s) of portable jack(s) were not legibly and permanently marked in a prominent location on the jack(s) by casting, stamping, or other suitable means. a) In the Mechanics Building 64, the Duro Mfg. Co. Ltd Portable Auto-Lift used for light pick ups did not have a visible rated load marked on the jack.
Recent events (2)
- — I (S) $4000
- — Z (S) $4000
1910.244 A02 VI A
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.244(a)(2)(vi)(a): Each jack used constantly or intermittently at a single locality was not thoroughly inspected at least once every six months. a) In the Mechanics Building 64, the Duro Mfg. Co. Ltd Portable Auto-Lift used for light pick ups had no record of inspections.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. a) In Building 63, the OSC 419 swamp cooler was powered by an extension cord. b) In Building 10, the Dewalt DW 872 Chop saw was powered by an extension cord.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.303 F02
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $15,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. a) Building 9, outside power panel on the East and North east corner next to the transformer bank were not labeled. b) At Building 11, circuit breaker in the manual center/right to know center breaker #1, circuit breaker panel A, was not labeled. c) At the Mechanic Building 64, Gray electrical power panel next to the main power panel, circuit breakers #14,16 and 18 were not labeled. The SOC Nevada LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(f)(2), which was contained in OSHA inspection number 904816 citation number 1, item number 10 and was affirmed as a final order on 09/03/2013 with respect to a workplace located at US Army Depot, Hawthorne, NV 89415.
Recent events (2)
- — I (R) $0
- — Z (R) $15000
1910.305 J01 I
- Issued
- Jan 14, 2015
- Abate by
- Feb 9, 2015
- Penalty
- Initial $20,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lamp holders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact. a) At Hawthorne Army Depot, Building 10 machine shop, the task lighting for Hammond Tool, USN 1719 serial 9428, Wet Grinder did not have a light bulb. The SOC Nevada LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(j)(1)(I), which was contained in OSHA inspection number 904816 citation number 1, item number 12 and was affirmed as a final order on 09/03/2013 with respect to a workplace located at US Army Depot, Hawthorne, NV 89415.
Recent events (2)
- — I (R) $0
- — Z (R) $20000
More inspections at SOC Nevada LLC