BOLINGBROOK, IL —
OSHA Inspection: REVIVA LOGISTICS, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of REVIVA LOGISTICS, LLC in 1000 VETERANS PARKWAY, BOLINGBROOK, IL 60440 (NAICS 423130). OSHA activity number 340082841.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- REVIVA LOGISTICS, LLC
- Site address
- 1000 VETERANS PARKWAY
- City
- BOLINGBROOK
- State
- IL
- ZIP
- 60440
- Mailing
- 1000 VETERANS PARKWAY, BOLINGBROOK, IL 60440
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423130
- Employees
- 26
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.37 A03
- Issued
- May 11, 2015
- Penalty
- Initial $2,380 · Current $1,666 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit routes must be free and unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route. The exit access must not go through a room that can be locked, such as a bathroom, to reach an exit or exit discharge, nor may it lead into a dead-end corridor. Stairs or a ramp must be provided where the exit route is not substantially level. a. On or about November 14, 2014, in the main building, employees of Kann Enterprises, INC., were required to operate forklifts and move pallets of tires on a daily basis. The north / central exit route was blocked by tires and pallets. Employees were thereby exposed to the hazards associated with blocked exits.
Recent events (2)
- — I (S) $1666
- — Z (S) $2380
1910.151 C
- Issued
- May 11, 2015
- Penalty
- Initial $1,785 · Current $1,250 Reduced
General-duty citation text
29 CFR 1910.151(c): Where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use. [63 FR 33450, June 18, 1998] a. On or about November 14, 2014, in the warehouse area, employees of Kann Enterprises, INC., were required to add water to the forklift batteries that contained sulfuric acid, a corrosive liquid. The employees were not provided with suitable facilities for quick drenching or flushing of eyes. The facility had a portable eye wash station that had no water in it. Employees were thereby exposed to the hazards associated with chemical contact.
Recent events (2)
- — I (S) $1249.5
- — Z (S) $1785
1910.303 B01
- Issued
- May 11, 2015
- Abate by
- Jun 26, 2015
- Penalty
- Initial $3,500 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.303(b)(1): Examination. Electric equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. a. On or about November 14, 2014, in the shipping / receiving area, employees of Kann Enterprises, INC. were required to operate forklifts and move pallets of tires on a daily basis. Emergency exit signs with exposed wires were hanging in the racks and aisle ways. Employees were thereby exposed to electrocution hazards. b. On or about November 14, 2014, in the shipping / receiving area, employees of Kann Enterprises, INC. were required to operate forklifts and move pallets of tires on a daily basis. Adjustable dock light fixtures that were present and / or in use (live) had exposed wire. Employees were thereby exposed to electrocution hazards.
Recent events (2)
- — I (S) $2450
- — Z (S) $3500
1910.303 G01
- Issued
- May 11, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. a. On or about November 14, 2014, at the above located workplace, employees of Kann Enterprises, INC., were required to work near and around a 480 volt power distribution box. Sufficient access and working space was not provided and maintained about the power distribution box. The area around the power distribution box was cluttered with packaging material and pallet appendages. Employees were thereby exposed to electrical hazards. b. On or about November 14, 2014, at the above located workplace, employees of Kann Enterprises, INC., were required to work near and around battery chargers. Sufficient access and working space was not provided and maintained about the battery chargers. The area around the battery charges was cluttered with packaging material, wooden slats (with nails), and other debris. Employees were thereby exposed to electrical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 I
- Issued
- May 11, 2015
- Penalty
- Initial $2,100 · Current $1,470 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. a. On or about November 14, 2014, in the shipping / receiving area, employees of Kann Enterprises, INC., were required to operate forklifts and move pallets of tires. Adjustable dock lighting apparatus' were present and powered by conductors not properly protected from abrasion in accordance with OSHA standards, thereby exposing employees to the hazards associated with electricity (electrocution, fire, and arc flash).
Recent events (2)
- — I (S) $1470
- — Z (S) $2100
1910.305 B02 I
- Issued
- May 11, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. a. On or about November 14, 2014, in the shipping and receiving area, employees of Kann Enterprises, Inc., were required to operate forklifts and move pallets of tires daily. A live junction box (120 volt) was not provided with a cover. Employees were thereby exposed to the hazards associated with energized electrical parts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B06
- Issued
- May 11, 2015
- Abate by
- Jun 26, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(6): Exit sign(s) were not suitably illuminated by a reliable light source which gave a value of at least five foot-candles (54 lux) on the illuminated surface: a. On or about November 14, 2014, in the shipping and receiving area, employees of Kann Enterprises, Inc., were required to operate forklifts and move pallets of tires daily. All emergency exit signs throughout the facility were not illuminated by a reliable light source.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 C04
- Issued
- May 11, 2015
- Abate by
- Jun 26, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): The employer shall assure that portable fire extinguishers are maintained in a fully charged and operable condition and kept in their designated places at all times except during use. Warehouse - On or about November 14, 2014, employees of Kann Enterprises, INC., were required to operate forklifts and move pallets of tires on a daily basis. The employer did not ensure that all portable fire extinguishers were kept in their designated places at all times. Approximately five fire extinguishers in the east corridor (receiving dock) of the warehouse were not present at their designated location.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 423130)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340082841.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.