Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,124Inspections Most recent open 2026-08-25 Last loaded 2026-08-28

OSHA Inspection: THE FARFIELD COMPANY

Programmed Related inspection · Safety discipline

On , OSHA opened a programmed Related safety inspection of THE FARFIELD COMPANY in 333 EVANSDALE DR. AGRICULTURAL SCIENCE BUILDING, MORGANTOWN, WV 26506 (NAICS 238210). OSHA activity number 340095934.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Farfield Company for free Get an email when a new federal OSHA severe-injury report for The Farfield Company is published. One employer, no account, unsubscribe in one click.
Site address
333 EVANSDALE DR. AGRICULTURAL SCIENCE BUILDING
City
MORGANTOWN
State
WV
ZIP
26506
Mailing
312 EAST MEADOW VALLEY ROAD, LITITZ, PA 17543
Inspection type
Programmed Related (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
11
Ownership type
Private (A)

3 citations on file for this inspection.

1926.403 A

Serious Gravity 5 1 instance 30 exposed
Issued
Dec 1, 2014
Abate by
Dec 26, 2014
Penalty
Initial $3,600 · Current $2,160 Reduced
29 CFR 1926.403(a): All electrical conductors and equipment were not approved:    a.)  The Farfield Company, Agricultural Sciences Building:  On or about 11/17/14, the shop made temporary power receptacle boxes had not been approved for use.    ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
  • · I (S) $2160
  • · Z (S) $3600

1926.403 G

Serious Gravity 5 1 instance 30 exposed
Issued
Dec 1, 2014
Abate by
Dec 26, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.403(g): Electrical equipment which was used did not have the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product could be identified:  a.)  The Farfield Company, Agricultural Sciences Building:  On or about 11/17/14, the shop made temporary power receptacle box was not marked with the manufacturer's information.  ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.405 A02 II B

Repeat Gravity 5 1 instance 30 exposed
Issued
Dec 1, 2014
Abate by
Dec 26, 2014
Penalty
Initial $7,200 · Current $4,320 Reduced
29 CFR 1926.405(a)(2)(ii)(B): Runs of open conductors used as temporary wiring branch circuits were located where the conductors would be subject to physical damage, branch circuit conductors were laid on the ground:    a.)  The Farfield Company, Agricultural Sciences Building:  On or about 11/17/14, the romex cable used to supply power to the temporary receptacle boxes were not protected from physical damage.    The Farfield Company was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1926.405(a)(2)(ii)(B), which was contained in OSHA inspection number 315886903, Citation 01, item number 001 and was affirmed as a final order on 02/06/12, with respect to a workplace located at Henderson Biobehavioral Health Building, State College, PA 16802.      ABATEMENT DOCUMENTATION IS REQUIRED
Recent events (2)
  • · I (R) $4320
  • · Z (R) $7200

View The Farfield Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 340095934.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.