Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WESTMINSTER COMMUNITIES OF FLORIDA

Programmed Related inspection · Safety discipline

On , OSHA opened a programmed Related safety inspection of WESTMINSTER COMMUNITIES OF FLORIDA in 1095 PINELLAS POINT DRIVE SOUTH, SAINT PETERSBURG, FL 33705 (NAICS 623311). OSHA activity number 340105949.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Westminster Communities of Florida — free Get an email when a new federal OSHA severe-injury report for Westminster Communities of Florida is published. One employer, no account, unsubscribe in one click.
Site address
1095 PINELLAS POINT DRIVE SOUTH
City
SAINT PETERSBURG
State
FL
ZIP
33705
Mailing
1095 PINELLAS POINT DRIVE SOUTH, SAINT PETERSBURG, FL 33705
Inspection type
Programmed Related (J)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623311
Employees
243
Ownership type
A

6 citations on file for this inspection.

1910.303 H05 III A

Serious Gravity 10 2 instances 2 exposed
Issued
Mar 30, 2015
Penalty
Initial $6,300 · Current $3,780 Reduced
29 CFR 1910.303(h)(5)(iii)(A): The entrances shall be kept locked unless they are under the observation of a qualified person at all times; and      a) At the establishment - no qualified person was in the boiler room, while employees were exposed to an electrical hazard, on or about 11/26/2014.
Recent events (2)
  • — I (S) $3780
  • — Z (S) $6300

1910.303 H05 III B

Other-than-serious 1 instance 2 exposed
Issued
Mar 30, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(h)(5)(iii)(B): Permanent and conspicuous warning signs shall be provided, reading substantially as follows:      a) At the establishment - no sign was posted with "DANGER -- HIGH VOLTAGE -- KEEP OUT ", outside the boiler room door, on or about 11/26/2014
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 10 1 instance 2 exposed
Issued
Mar 30, 2015
Abate by
May 14, 2015
Penalty
Initial $6,300 · Current $3,780 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:      a) At the establishment - no training was conducted for maintenance technicians, on or about 11/26/2014
Recent events (2)
  • — I (S) $3780
  • — Z (S) $6300

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Mar 30, 2015
Abate by
May 14, 2015
Penalty
Initial $6,300 · Current $3,780 Reduced
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.      a) At the establishment - maintenance technicians are exposed to an electrical shock hazard, while conducting maintenance on energized electrical outlets, on or about 11/26/2014.
Recent events (2)
  • — I (S) $3780
  • — Z (S) $6300

1910.335 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Mar 30, 2015
Abate by
May 14, 2015
Penalty
Initial $6,300 · Current $3,780 Reduced
29 CFR 1910.335(a)(1): Employees working in areas where there were potential electrical hazards were not provided with, and/or did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:       a) In the electrical room - following a lighting strike, no personal protective equipment was  provided to maintenance technicians on call when working on electrical equipment, exposing the worker to an arc flash, on or about 11/26/2014.
Recent events (2)
  • — I (S) $3780
  • — Z (S) $6300

1910.38 C04

Other-than-serious 1 instance 2 exposed
Issued
Mar 30, 2015
Abate by
May 14, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.38(c)(4): Procedures to account for all employees after evacuation:    1. The employer's emergency action plan did not include procedures to account for all employees after an evacuation, on or about 11/26/2014.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Westminster Communities of Florida's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340105949.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.