Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ROHR INDUSTRIES, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ROHR INDUSTRIES, INC. in 201 STACKPOLE STREET SUITE 35 B, SAINT MARYS, PA 15857 (NAICS 332710). OSHA activity number 340125996.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Rohr Industries, INC. — free Get an email when a new federal OSHA severe-injury report for Rohr Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
201 STACKPOLE STREET SUITE 35 B
City
SAINT MARYS
State
PA
ZIP
15857
Mailing
P.O. BOX 151 STACKPOLE STREET SUITE 35B, SAINT MARYS, PA 15857
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
20
Ownership type
A

12 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $2,000 · Current $1,000 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees:      A.)  Rohr Industries, Inc./Shop Area By Tarped Warehouse Entrance: On or about November 21, 2014, and at times prior thereto, Employees were potentially exposed to fire hazards from the improper use and installation of a Torpedo heater.  The Desa Model torpedo heater was utilized improperly in that it was used less than 10-feet from combustible materials such as a fiberboard drum, plastic tarp, and plastic containers.  In addition, the Torpedo heater was not being operated on a stable surface.  The torpedo heater was being operated off the ground from the top of a fiberboard drum
Recent events (3)
  • — F (S) $1000
  • — C (S) $2000
  • — Z (S) $2000

1910.147 C01

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:      A.)  Rohr Industries, Inc. - On or about 12/9/14, the company did not have a lockout/tagout program consisting of affected and authorized employee training, specific procedures, periodic inspections, and lockout/tagout hardware .  The employees performed work on equipment including but not limited to, Mori Seiki Lathe ZL - 15.  Employees performed servicing and maintenance on equipment which included, but was not limited to, preventative maintenance and repairs.
Recent events (3)
  • — F (S) $800
  • — C (S) $1600
  • — Z (S) $1600

1910.212 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $2,400 · Current $1,200 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    A.)  Rohr Industries, Inc.; shop area - On or about 12/9/14, the interlocks were not operational on the CNC lathes.  These CNC Lathes included but were not limited to, Mori Seiki Lathe ZL-15, #14.  Employees were able to reach into the machinery while it was still running.
Recent events (3)
  • — F (S) $1200
  • — C (S) $2400
  • — Z (S) $2400

1910.219 D01

Serious Gravity 5 2 instances 2 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):    A.)  Rohr Industries, Inc.; Machine shop - On or about, 12/9/14, a CNC lathe (Serial #2619) had a partially unguarded belt/pulley system on the side of it.  The side housing of the machine did not adequately guard the lower part of the belt/pulley system. The pulley/belt system was located 2 feet above floor level.      B.)  Rohr Industries, Inc., Machine Shop - On or about, 12/9/14, an air compressor had an unguarded belt.  The pulley/belt system was located 3 feet above the floor level.
Recent events (3)
  • — F (S) $800
  • — C (S) $1600
  • — Z (S) $1600

1910.303 B02

Serious Gravity 5 3 instances 2 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:      A.)  Rohr Industries, Inc. - On or about 12/9/14, fans were being utilized to dry parts in the machine shop.  The fans were 'household type' fans and were not listed and labeled to be used in an industrial environment.    B.)  Rohr Industries, Inc. - On or about 12/9/14, a household type extension cord without a grounding prong was being utilized to power the ventilation system.  The cord was not listed and labeled to be used in an industrial environment.
Recent events (3)
  • — F (S) $800
  • — C (S) $1600
  • — Z (S) $1600

1910.303 G01 I

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1:      A.)  Rohr Industries, Inc.: Machine shop - On or about 12/9/14, an air compressor was located within 1 foot of the front of an electrical panel box.   The electrical panel box serviced the CNC machines.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.303 F01

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    A.)  Rohr Industries, Inc.; Machine shop - On or about 12/9/14, an electrical panel box that powered multiple CNC Lathes did not have the breakers labeled to identify what each breaker powered.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 3 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $1,200 · Current $600 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:      A.)  Rohr Industries, Inc.; Machine shop - On or about 12/9/14, and at times prior thereto, the company was utilizing extension cords in lieu of permanent wiring to power heaters, lighting, ventilation system and shop vac.    The extension cords were strung together to reach outlets.
Recent events (3)
  • — F (S) $600
  • — C (S) $1200
  • — Z (S) $1200

1910.305 G01 IV C

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were run through doorways, windows or floors.      A.)  Rohr Industries, Inc.; Machine shop  - On or about 12/9/14, the company was utilizing an extension cord to power a shop vac by Press #11.  The extension cord was run from the adjacent room through a door way and down to the shop vac.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 1 1 instance 1 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:      A.)  Rohr Industries, Inc.; Machine Shop - On or about 12/9/14, the company had installed a knockout type receptacle  box that was free hanging.  The box had not been provided with any strain relief to prevent damage.  The receptacle outlet box was utilized to power a heater.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 1 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $1,200 · Current $600 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:      A.)  Rohr Industries, Inc.: Machine Shop - On or about 12/9/14, the air compressor did not have a cover on the front of a junction box.  Exposed wires were sticking out of the box.
Recent events (3)
  • — F (S) $600
  • — C (S) $1200
  • — Z (S) $1200

1910.303 B01 II

Serious Gravity 1 1 instance 1 exposed
Issued
Jan 28, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:      A.)  Rohr Industries, Inc.; Machine shop; panel box by air compressor - On or about 12/9/14, an electrical panel box had a cover on it which was not flush/secured to the actual box.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

View Rohr Industries, INC.'s full OSHA safety record →