Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SOLARIS OILFIELD INFRASTRUCTURE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SOLARIS OILFIELD INFRASTRUCTURE in 100 ROSS DRIVE, EARLY, TX 76802 (NAICS 333132). OSHA activity number 340126697.

Watch Solaris Oilfield Infrastructure — free Get an email when a new federal OSHA severe-injury report for Solaris Oilfield Infrastructure is published. One employer, no account, unsubscribe in one click.
Site address
100 ROSS DRIVE
City
EARLY
State
TX
ZIP
76802
Mailing
100 ROSS DRIVE, EARLY, TX 76802
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333132
Employees
108
Ownership type
A

4 citations on file for this inspection.

1910.37 B02

Serious Gravity 5 2 instances 10 exposed
Issued
Abate by
Penalty
Initial $3600.00 · Current $2160.00 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit".   On or about December 8, 2014, and times prior thereto, inside the production shop, exit signs were not installed above the east and west emergency exit doors exposing employees to fire hazards.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

1910.305 B01

Serious Gravity 1 2 instances 10 exposed
Issued
Abate by
Penalty
Initial $2700.00 · Current $1620.00 Reduced
29 CFR 1910.305(b)(1): Unused openings in boxes, cabinets, or fittings were not effectively closed.    On or about December 8, 2014, and times prior thereto, inside the production shop, electrical outlet boxes were missing knock-out plugs exposing employees to electrical hazards:        a)      In bay 1, an outlet box was used to energize portable grinders.          b)     In the storage area, an outlet box was used to energize an electrode stabilizing oven.
Recent events (2)
  • — I (S) $1620
  • — Z (S) $2700

1910.305 G01 IV A

Serious Gravity 1 1 instance 10 exposed
Issued
Penalty
Initial $2295.00 · Current $1377.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.    On or about December 8, 2014, and times prior thereto, inside the production shop, an extension cord, wrapped around a solid conduit, was used as permanent wiring to energize the Lenco electrode stabilizing oven exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $1377
  • — Z (S) $2295

1910.334 A02 I

Serious Gravity 1 1 instance 10 exposed
Issued
Penalty
Initial $2295.00 · Current $1377.00 Reduced
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).    On or about December 8, 2014, and times prior thereto, inside the production shop, the employees used an extension cord with a missing ground pin to energize a Dewalt grinder exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $1377
  • — Z (S) $2295