EL PASO, TX ·
OSHA Inspection: DEAN DAIRY HOLDINGS, LLC
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of DEAN DAIRY HOLDINGS, LLC in 600 N. PIEDRAS ST, EL PASO, TX 79923 (NAICS 311511). OSHA activity number 340126838.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEAN DAIRY HOLDINGS, LLC
- Site address
- 600 N. PIEDRAS ST
- City
- EL PASO
- State
- TX
- ZIP
- 79923
- Mailing
- 600 N. PIEDRAS ST BOX 3008, EL PASO, TX 79923
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311511
- Employees
- 1903
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.119 F01 III D
- Issued
- May 29, 2015
- Abate by
- Jun 17, 2015
- Penalty
- Initial $3,740 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.119(f)(1)(iii)(D): The employer's written operating procedures covering operating limits did not address quality control for raw materials and control of hazardous chemical inventory levels: Ammonia Refrigeration System: The employer did not have written procedures that addressed the grade and delivery of ammonia. This condition that may expose employees to an inhalation hazards from an accidental release of ammonia.
Recent events (2)
- · I (O) $2000
- · Z (S) $3740
1910.119 J04 III
- Issued
- May 29, 2015
- Abate by
- Jun 17, 2015
- Penalty
- Initial $3,740 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment to maintain its mechanical integrity, was not consistent with applicable manufacturer's recommendations and good engineering practices, or more frequently determined to be necessary by prior operating experience. Ammonia Refrigeration System: The employer did not inspect or test the safety shutdown systems at least yearly for the Ammonia Refrigeration system and with applicable good engineering practices.
Recent events (2)
- · I (S) $3000
- · Z (S) $3740
1910.119 J05
- Issued
- May 29, 2015
- Abate by
- Jun 17, 2015
- Penalty
- Initial $3,740 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): Equipment deficiencies. The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation. Ammonia Refrigeration System, South Engine Room wall: there was a hole and it was outside of acceptable limits.
Recent events (2)
- · I (O) $2000
- · Z (S) $3740
1910.119 N
- Issued
- May 29, 2015
- Abate by
- Jun 17, 2015
- Penalty
- Initial $3,740 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.119(n): Emergency planning and response. The employer did not establish and implement an emergency action plan for the entire plant in accordance with the provisions of 29 CFR 1910.38. In addition, the emergency action plan did not include procedures for handling small releases. Ammonia Refrigeration System: The employer did not have an emergency action plan that differentiated between small and large ammonia releases. This condition exposes employees to inhalation hazards from an unexpected release of ammonia.
Recent events (2)
- · I (O) $2000
- · Z (S) $3740
1910.134 F01
- Issued
- May 29, 2015
- Abate by
- Jun 17, 2015
- Penalty
- Initial $2,805 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.134(f)(1): The employer did not ensure that employee(s) required to use a tight-fitting facepiece respirator passed the appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT): Ammonia Refrigeration System: The employer required the use of tight fitting respirators during repairs and system modifications and employees had not been fit tested.
Recent events (2)
- · I (S) $2000
- · Z (S) $2805
More inspections at Dean Dairy Holdings, LLC
View Dean Dairy Holdings, LLC's full OSHA safety record →
More inspections in this industry (NAICS 311511)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 340126838.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.