RACINE, WI ·
OSHA Inspection: PUDGY'S PUB, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of PUDGY'S PUB, INC. in 7800 WASHINGTON AVENUE, RACINE, WI 53406 (NAICS 722410). OSHA activity number 340130731.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PUDGY'S PUB, INC.
- Site address
- 7800 WASHINGTON AVENUE
- City
- RACINE
- State
- WI
- ZIP
- 53406
- Mailing
- 7800 WASHINGTON AVENUE, RACINE, WI 53406
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 722410
- Employees
- 2
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 G01 I A
- Issued
- Feb 19, 2015
- Abate by
- Mar 10, 2015
- Penalty
- Initial $2,000 · Current $1,020 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: (a) The employer did not ensure that an electrical panel had a depth clearance of at least 3 feet, exposing employees to electrical hazards.
Recent events (2)
- · I (S) $1020
- · Z (S) $2000
1910.303 G01 I B
- Issued
- Feb 19, 2015
- Abate by
- Mar 10, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : (a) The employer did not ensure that an electrical panel had a width clearance of at least 30 inches, exposing employees to electrical hazards.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.334 A04
- Issued
- Feb 19, 2015
- Abate by
- Mar 17, 2015
- Penalty
- Initial $2,800 · Current $1,428 Reduced
General-duty citation text
29 CFR 1910.334(a)(4): Portable electric equipment and flexible cords that was used in highly conductive work locations (such as those inundated with water or other conductive locations) or in job locations where employees were likely to contact water or conductive liquids were not approved for those locations. (a) The employer did not ensure that a scrubbing machine appliance used in a wet environment had GFCI protection, exposing employees to electrical shock hazards. In The Alternative: 29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) The employer did not ensure that a scrubbing machine appliance used in a wet environment had GFCI protection, exposing employees to electrical shock hazards.
Recent events (2)
- · I (S) $1428
- · Z (S) $2800