Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: ADVANCED WOOD TECHNOLOGIES, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of ADVANCED WOOD TECHNOLOGIES, INC. in 115 AUSTIN ST., MONROE, LA 71202 (NAICS 337110). OSHA activity number 340131218.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Advanced Wood Technologies, INC. for free Get an email when a new federal OSHA severe-injury report for Advanced Wood Technologies, INC. is published. One employer, no account, unsubscribe in one click.
Site address
115 AUSTIN ST.
City
MONROE
State
LA
ZIP
71202
Mailing
910 ITALIANA PLACE, WEST MONROE, LA 71291
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337110
Employees
8
Ownership type
Private (A)

9 citations on file for this inspection.

1910.22 A01

Serious Gravity 10 1 instance 3 exposed
Issued
Jan 30, 2015
Abate by
Mar 2, 2015
Penalty
Initial $2,800 · Current $1,680 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition:      a.     All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition.  This violation occurred on or about December 10, 2014, when combustible, class II, wood dust accumulated on the structural members, stored materials, and machinery throughout the workshop creating a potential fire and/or explosion hazard.
Recent events (2)
  • · I (S) $1680
  • · Z (S) $2800

1910.22 A02

Serious Gravity 10 1 instance 3 exposed
Issued
Jan 30, 2015
Abate by
Feb 14, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a)(2): Floor(s) of workroom(s) were not maintained in a clean and, so far as possible, a dry condition:    a.     The employer did not ensure that floors of workrooms were maintained in a clean condition.  This violation occurred on or about December 10, 2014, when the employer did not maintain the floors free of combustible wood dust.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.37 A03

Serious Gravity 1 2 instances 3 exposed
Issued
Jan 30, 2015
Abate by
Feb 14, 2015
Penalty
Initial $1,020 · Current $612 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed    a.  The employer did not ensure that exit routes were kept free and unobstructed.  This violation occurred on or about December 10, 2014, when the South emergency exit near the garage door was blocked by floor fans.    b.  The employer did not ensure that exit routes were kept free and unobstructed.  This violation occurred on or about December 10, 2014, when the East emergency exit near the garage door was blocked by floor fans.
Recent events (2)
  • · I (S) $612
  • · Z (S) $1020

1910.303 G01 I A

Serious Gravity 1 2 instances 3 exposed
Issued
Jan 30, 2015
Penalty
Initial $867 · Current $520 Reduced
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:    a.  The employer did not ensure that electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, that the depth of the working space in the direction of access to live parts was not less than indicated in Table S-1 of Subpart S of Part 1910.  This violation occurred on or about December 10, when the electrical service entrance and circuit breaker panels on the South side of the building did not have at least three (3) feet of clearance in the direction of access as required in Table S-1.    b.  The employer did not ensure that electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, that the depth of the working space in the direction of access to live parts was not less than indicated in Table S-1 of Subpart S of Part 1910.  This violation occurred on or about December 10, when the circuit breaker panels for the dust collection system on the West side of the building did not have at least three (3) feet of clearance in the direction of access as required in Table S-1.
Recent events (2)
  • · I (S) $520
  • · Z (S) $867

1910.307 C02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Jan 30, 2015
Abate by
Mar 16, 2015
Penalty
Initial $2,000 · Current $1,200 Reduced

Hazardous substances E200

29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present:    a.  The employer did not ensure that electrical equipment was approved for the combustible properties of the dust that was present.  This violation occurred on or about December 10, 2014, when the electrical installation included junction boxes and outlets that were not approved for the Class 2, Division 2 location containing combustible wood dust.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.305 B02 I

Serious Gravity 5 3 instances 3 exposed
Issued
Jan 30, 2015
Abate by
Mar 2, 2015
Penalty
Initial $0 · Current $0

Hazardous substances E200

29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:    a.  The employer did not ensure that each pull box, junction box, and fitting was provided with covers approved for the purpose.  This violation occurred on or about December 10, 2014, when junction/pull box powering the rip saw was not provided with a cover approved for the purpose.     b.  The employer did not ensure that each pull box, junction box, and fitting was provided with covers approved for the purpose.  This violation occurred on or about December 10, 2014, when junction/pull box along the ceiling above the table saws was not provided with a cover approved for the purpose.     c.  The employer did not ensure that each pull box, junction box, and fitting was provided with covers approved for the purpose.  This violation occurred on or about December 10, 2014, when junction/pull box attached to conduit running down the ductwork to the table saws was not provided with a cover approved for the purpose.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.304 G05

Other-than-serious 1 instance 1 exposed
Issued
Jan 30, 2015
Abate by
Feb 14, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a.  The employer did not ensure that the path to ground from circuits, equipment, and enclosures was permanent, continuous, and effective.  This violation occurred on or about December 10, 2014, when the ground pin was missing on a flexible cord set being used to power the bleed water pump from the compressor.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 G01 IV D

Other-than-serious 1 instance 1 exposed
Issued
Jan 30, 2015
Abate by
Feb 14, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces:  a.  The employer did not ensure that flexible cords were not attached to building surfaces.  This violation occurred when a flexible cord set was attached to the building in order to extend power to the bore machine.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 G02 III

Other-than-serious 1 instance 1 exposed
Issued
Jan 30, 2015
Abate by
Feb 14, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  a.  The employer did not ensure that flexible cords and cables were connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted tot he joints or terminal screws.  This violation occurred on or about December 10, 2014 when the flexible power cord to the bore machine was damaged from strain.