Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ASHLAND COLD STORAGE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ASHLAND COLD STORAGE in 1556 W. 43RD STREET, CHICAGO, IL 60609 (NAICS 493120). OSHA activity number 340131721.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ashland Cold Storage — free Get an email when a new federal OSHA severe-injury report for Ashland Cold Storage is published. One employer, no account, unsubscribe in one click.
Site address
1556 W. 43RD STREET
City
CHICAGO
State
IL
ZIP
60609
Mailing
1556 W. 43RD STREET, CHICAGO, IL 60609
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
61
Ownership type
A

1 citation on file for this inspection.

1910.119 D03 II

Serious Gravity 5 5 instances 3 exposed
Issued
Jun 1, 2015
Penalty
Initial $3,273 · Current $1,960 Reduced
29 CFR 1910.119(d)(3)(ii): The employer shall document that equipment complies with recognized and generally accepted good engineering practices.    On or about January 14, 2015, the employer did not document that its equipment complies with recognized and generally accepted good engineering practice according to the ASHRAE-15 and IIAR-2 ANSI Standards or equivalent. Examples include, but are not limited to:    a. West end of building - Outside the "Southeast" and "West", engine room doors there were no visual and audible ammonia alarms. Also the meaning of each alarm was not marked by signs near the annunciators.     b. West end of building - Inside the "West", engine room the were no audible ammonia alarms. Also the meaning of each alarm was not marked by signs near the annunciators.     c. Mezzanine engine room - Remote control of the mechanical equipment in the refrigeration machinery room was not provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency.    d. Mezzanine engine room - Emergency shutdown procedures including precautions to be observed in case of breakdown, or leak, were not posted outside of each engine room, immediately adjacent to each door.    e. Mezzanine engine room - The "North" double doors were not tight fitting, permitting passage of escaping ammonia to other work areas.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $3273

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340131721.