SAN ANTONIO, TX —
OSHA Inspection: CENTRAL TEXAS EXPRESS METALWORK, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CENTRAL TEXAS EXPRESS METALWORK, LLC in 420 MILAM, SAN ANTONIO, TX 78202 (NAICS 332312). OSHA activity number 340139278.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CENTRAL TEXAS EXPRESS METALWORK, LLC
- Site address
- 420 MILAM
- City
- SAN ANTONIO
- State
- TX
- ZIP
- 78202
- Mailing
- 420 MILAM, SAN ANTONIO, TX 78202
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332312
- Employees
- 25
- Ownership type
- A
Citations
7 citations on file for this inspection.
5(a)(1)
- Issued
- May 1, 2015
- Abate by
- May 16, 2015
- Penalty
- Initial $2,400 · Current $1,440 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazards of being struck-by fragments of Polyvinyl Chloride (PVC) plastic pipe in the event that the PVC plastic pipe ruptured: Room containing the Burn Table: On or about November 25, 2014, employees were exposed to the hazards of being struck by fragments of Polyvinyl Chloride (PVC) plastic pipe, while the pipe was being used to transport compressed air, at approximately 118 psi, to tools and equipment, while the pipe was not in a conduit or casing of sufficient strength to provide protection from external damage and deterioration.
Recent events (2)
- — I (S) $1440
- — Z (S) $2400
1910.303 B02
- Issued
- May 1, 2015
- Abate by
- May 16, 2015
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Main Production Floor: On or about November 25, 2014, employees were exposed to an electrical hazard from two 240 Vac receptacle pendants, in which the receptacles were installed in an enclosure not designed for the application, while using them to supply electricity to portable welders. b) Main Production Floor: On or about November 25, 2014, employees were exposed to an electrical hazard from a 240 Vac job made extension cord, in which the receptacle was installed in an enclosure not designed for the application, while using it to supply electricity to portable welders.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.303 G02 II
- Issued
- May 1, 2015
- Abate by
- May 16, 2015
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment is likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage. Main Production Floor: On or about November 25, 2014, employees were exposed to the hazards of being struck by falling objects, from bulbs of an 8 ft. fluorescent light fixture mounted above the press for illumination that were not protected from breakage, while using the mechanical press to bend metal plates.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.305 B01 II
- Issued
- May 1, 2015
- Abate by
- May 16, 2015
- Penalty
- Initial $2,400 · Current $1,440 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed: Main Production Floor: On or about November 25, 2014, employees were exposed to an electrical hazard, from the circuit breaker panel that had missing circuit breaker blanks, while operating the circuit breakers in Panel B for lighting.
Recent events (2)
- — I (S) $1440
- — Z (S) $2400
1910.305 B02 I
- Issued
- May 1, 2015
- Abate by
- May 16, 2015
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Main Production Floor: On or about November 25, 2014, employees were exposed to an electrical hazard from a two gang 120 Vac receptacle pendant, in which the receptacle's face plate was damaged, while using it to supply electricity to portable tools and equipment.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.305 G02 III
- Issued
- May 1, 2015
- Abate by
- May 16, 2015
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) Room containing Burn Table: On or about November 25, 2014, employees were exposed to an electrical hazard, where there was no strain relief on the main power supply wiring, while using a Hypotherm Powermax 1650 Plasma Cutting Machine that was hard wired into a circuit breaker panel. b) Production Floor: On or about November 25, 2014, employees were exposed to an electrical hazard, where there was no strain relief on the power cord of a fluorescent light fixture, while using it to illuminate the work location along the south wall.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.334 A02 I
- Issued
- May 1, 2015
- Abate by
- May 16, 2015
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket). Cord and plug connected equipment and flexible cord sets (extension cords) which remain connected once they are put in place and are not exposed to damage need not be visually inspected until they are relocated: Main Production Floor: On or about November 25, 2014, employees were exposed to an electrical hazard while using a Maxx Air, 30 inch, pedestal fan, which was plugged into an energized circuit and the grounding pin of the plug was missing.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
More inspections at Central Texas Express Metalwork, LLC
View Central Texas Express Metalwork, LLC's full OSHA safety record →
More inspections in this industry (NAICS 332312)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340139278.