PAGO PAGO, AS —
OSHA Inspection: K & K CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of K & K CORPORATION in MAIN RD, TAFUNA INDUSTRIAL PARK, PAGO PAGO, AS 96799 (NAICS 493110). OSHA activity number 340145861.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- K & K CORPORATION
- Site address
- MAIN RD, TAFUNA INDUSTRIAL PARK
- City
- PAGO PAGO
- State
- AS
- ZIP
- 96799
- Mailing
- P.O. BOX 7893, PAGO PAGO, AS 96799
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 8
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.305 G01 IV A
- Issued
- Feb 11, 2015
- Abate by
- Feb 24, 2015
- Penalty
- Initial $1,360 · Current $952 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a. On December 4, 2014, on the west wall of the warehouse, an electrical cord originated from the panel box on the ground floor and ran along wall and into the second floor.
Recent events (2)
- — I (S) $952
- — Z (S) $1360
1910.305 G02 II
- Issued
- Feb 11, 2015
- Abate by
- Feb 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap. On December 4, 2014, on the west wall of the warehouse, an electrical cord originated in the panel box located on the ground floor and ran along the wall to the second floor was spliced.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J01 I
- Issued
- Feb 11, 2015
- Abate by
- Feb 24, 2015
- Penalty
- Initial $1,020 · Current $714 Reduced
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located had live parts normally exposed to employee contact: a. On December 4, 2014, on the north wall on the second floor, the outlet receptacle providing power to the lights was missing the cover.
Recent events (2)
- — I (S) $714
- — Z (S) $1020
1910.37 A03
- Issued
- Feb 11, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a. On December 4, 2014, in the warehouse, the stairs to the second level were used to store tile and furniture reducing the width of the exit route.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at K & K Corporation
View K & K Corporation's full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in AS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340145861.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.