OSHA Inspection: PEDERNALES ELECTRIC COOPERATIVE, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PEDERNALES ELECTRIC COOPERATIVE, INC. in 1530 FM 2673, CANYON LAKE, TX 78130 (NAICS 238210). OSHA activity number 340154178.

Watch Pedernales Electric Cooperative, INC. — free Get an email when a new federal OSHA severe-injury report for Pedernales Electric Cooperative, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1530 FM 2673
City
CANYON LAKE
State
TX
ZIP
78130
Mailing
P.O. BOX 1, JOHNSON CITY, TX 78636
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
4
Ownership type
A

3 citations on file for this inspection.

1926.952 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $3000.00 Reduced
29 CFR 1926.952(a)(2): The employer did not ensure that the employee in charge conducts a job briefing that meets paragraph (b),(c) and (d) of this section with the employees involved before they start each job:  On or about December 18, 2014 and in times prior thereto, in the Hidden Forest Subdivision of the Canyon Lake District, electrical utility workers were rigging up to pull URD cable through underground risers located below 14.4 KVA power lines without conducting a job safety briefing to identify hazards and control measures, exposing employees to the hazards of electric shock.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1926.959 D01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $3000.00 Reduced
29 CFR 1926.959(d)(1): Mechanical equipment was not operated so that the minimum approach distance established by the employer was maintained:  On or about December 18, 2014 and in times prior thereto, employees were setting up a digger derrick truck to pull underground cable and failed to maintain a minimum 2'  2" approach distance, exposing employees to the hazards of electrical shock of 14.4 KVA.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1926.959 D02

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.959(d)(2): A designated employee other than the equipment operator did not observe the approach distance to exposed lines and equipment and provide timely warning before the minimum approach distance require by paragraph (d)(1) of the section was reached.:  On or about December 18, 2014 and in times prior thereto, a spotter was not designated to observe the digger derrick truck as the operator moved a spool of cable into position under overhead energized power lines. A 2' 2" minimum approach distance was not maintained. This condition exposed employees to a electric shock hazard of 14.4 KVA, located at the new power line construction site, in the Hidden Forest Subdivision.