Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SUMMER HOLIDAY HOTEL SAIPAN

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SUMMER HOLIDAY HOTEL SAIPAN in ALAIHAI AVE, SAIPAN, MP 96950 (NAICS 721110). OSHA activity number 340163476.

Watch Summer Holiday Hotel Saipan — free Get an email when a new federal OSHA severe-injury report for Summer Holiday Hotel Saipan is published. One employer, no account, unsubscribe in one click.
Site address
ALAIHAI AVE
City
SAIPAN
State
MP
ZIP
96950
Mailing
PMB A-4, P.O. BOX 10001, SAIPAN, MP 96950
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
8
Ownership type
A

3 citations on file for this inspection.

1910.305 J02 IV

Serious Gravity 1 1 instance 8 exposed
Issued
Penalty
Initial $1200.00 · Current $840.00 Reduced
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:    a)  On January 28, 2015, in the laundry room, a ground-fault circuit interrupter type receptacle was not installed in an outlet within 2 feet of a sink.
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200

1910.1200 E01

Serious Gravity 1 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $840.00 Reduced
29 CFR 1910.1200(e)(1): Employers did not develop, implement, and maintain at each workplace, a written hazard communication program which at least describes how the criteria specified in paragraphs (f), (g), and (h) of this section for labels and other forms of warning, material safety data sheets, and employee information and training were met (Referenced in 29 CFR 1926.59):     a) On January 28, 2015, a written hazard communication program was not developed for employees that worked with chemicals to include, but not limited to enamel paints, including Krylon spray cans, acid cleaner, pipe cleaner, pipe glue, roof cement, and solvents.
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200

1910.303 G01 I B

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater :   a)  On January 28, 2015, inside the maintenance shop, the electrical controller labeled "Green Pump", operating at 240 volts was blocked by debris and equipment.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340163476.