OSHA Inspection: CLIPPER EQUITY, LLC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CLIPPER EQUITY, LLC. in 98 MONTAGUE STREET, BROOKLYN, NY 11201 (NAICS 236118). OSHA activity number 340164292.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Clipper Equity, LLC. for free Get an email when a new federal OSHA severe-injury report for Clipper Equity, LLC. is published. One employer, no account, unsubscribe in one click.
Site address
98 MONTAGUE STREET
City
BROOKLYN
State
NY
ZIP
11201
Mailing
4611 12TH AVENUE SUIT 1L, BROOKLYN, NY 11219
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236118
Employees
15
Ownership type
A

2 citations on file for this inspection.

1926.403 I02 I

Serious Gravity 5 6 instances 6 exposed
Issued
Jun 19, 2015
Penalty
Initial $2,400 · Current $2,400
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.  Location: 98 Montague Street Brooklyn, NY / 2nd to the 12th floor.  On or About: 01/05/15.   a) Energized circuit breaker panels located from the 2nd to the 12th floors were not protected by a cover.  Energized parts not protected or guarded as employees worked in the area.
Recent events (1)
  • · Z (S) $2400

1926.405 G01 II

Serious Gravity 5 6 instances 6 exposed
Issued
Jun 19, 2015
Penalty
Initial $2,000 · Current $2,000
29 CFR 1926.405(g)(1)(ii): Attachment plugs for cords. If used as permitted in paragraphs (g)(1)(i)(C), (g)(1)(i)(F), or (g)(1)(i)(H) of this section, the flexible cord was not equipped with an attachment plug and was not energized from a receptacle outlet.  Location: 98 Montague Street Brooklyn, NY / 10th and 12th Floors.  On or About: 01/05/2015.  a) Electrical Heaters being used at the worksite were not equipped with attachment plugs.  Wires were connected into energized electrical panels.