Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NORTHERN EAGLE BEVERAGES, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NORTHERN EAGLE BEVERAGES, INC. in 7 RAILROAD AVE., ONEONTA, NY 13820 (NAICS 424810). OSHA activity number 340182500.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Northern Eagle Beverages, INC. — free Get an email when a new federal OSHA severe-injury report for Northern Eagle Beverages, INC. is published. One employer, no account, unsubscribe in one click.
Site address
7 RAILROAD AVE.
City
ONEONTA
State
NY
ZIP
13820
Mailing
P.O. BOX 827, ONEONTA, NY 13820
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424810
Employees
36
Ownership type
A

8 citations on file for this inspection.

1910.24 H

Serious Gravity 1 2 instances 10 exposed
Issued
Feb 6, 2015
Abate by
Mar 13, 2015
Penalty
Initial $2,100 · Current $1,470 Reduced
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms:  a)  Loading Dock Area, on or about 1/14/15:  Fixed stairway to mezzanine, with 16 risers, was not provided with midrails.  b)  Loading Dock Area, on or about 1/14/15:  Over the road stairway at the loading dock, with six risers, was not provided with standard stair rails on the left side descending.  Abatement certification must be submitted for these items.
Recent events (2)
  • — I (S) $1470
  • — Z (S) $2100

1910.37 A03

Serious Gravity 5 2 instances 20 exposed
Issued
Feb 6, 2015
Abate by
Feb 18, 2015
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:  a)  Non CEW warehouse, on or about 1/14/15:  Two exit doors to the dock area were blocked by pallets of beverages.  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.37 A04

Serious Gravity 5 1 instance 20 exposed
Issued
Feb 6, 2015
Abate by
Mar 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:  a)  CEW Warehouse, on or about 1/15/14:  Exit lighting was not working.  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 6, 2015
Abate by
Mar 13, 2015
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  a)  At the establishment, on or about 1/14/15:  The employer did not establish a lockout/tagout program and employee training when performing servicing and/or maintenance on, including, but not limited to hops pelletizer and associated processing equipment.  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.157 G02

Serious Gravity 1 1 instance 25 exposed
Issued
Feb 6, 2015
Abate by
Mar 13, 2015
Penalty
Initial $2,100 · Current $1,470 Reduced
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter:  a)  At the establishment, on or about 1/14/15:  Training was not provided to employees on the use of fire extinguishers and the hazards involved with incipient stage fire fighting.  *ABATEMENT NOTE:  By this date the employer must either correct the alleged violation or implement a Fire Safety Policy; as outlined in 29 CFR 1910.38 and 29 CFR 1910.39 which includes the evacuation requirements of 29 CFR 1910.157(b).  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $1470
  • — Z (S) $2100

1910.212 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 6, 2015
Abate by
Mar 13, 2015
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  a)  Hops pelletizing area, on or about 1/14/15:  Ingoing nip points and rotating parts at the beater arm on a Lawson Mills hops pelletizer was not adequately guarded in that you could operate the equipment with the hopper cover open.  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.303 G02 I

Serious Gravity 5 2 instances 2 exposed
Issued
Feb 6, 2015
Abate by
Mar 13, 2015
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:  a)  Loading Dock, on or about 1/14/15:  A duplex receptacle outlet and a switch on a floor box fan were not provided with covers, exposing live electrical parts.  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.304 G05

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 6, 2015
Abate by
Mar 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a)  Forklift area, on or about 1/14/15:  A Big Country barn fan was not grounded in that the ground pin was missing from the plug end.  Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Northern Eagle Beverages, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340182500.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.