Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. DEPARTMENT OF HOMELAND SECURITY, TRANSPORTATION SECURITY ADMINISTRATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF HOMELAND SECURITY, TRANSPORTATION SECURITY ADMINISTRATION in 5757 WAYNE NEWTON BOULEVARD, LAS VEGAS, NV 89119 (NAICS 481111). OSHA activity number 340196799.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Homeland Security, Transportation Security Administration — free Get an email when a new federal OSHA severe-injury report for U.S. Department of Homeland Security, Transportation Security Administration is published. One employer, no account, unsubscribe in one click.
Site address
5757 WAYNE NEWTON BOULEVARD
City
LAS VEGAS
State
NV
ZIP
89119
Mailing
6750 VIA AUSTI PARKWAY SUITE 200, LAS VEGAS, NV 89119
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
481111
Employees
1150
Ownership type
D

7 citations on file for this inspection.

1910.219 I02

Deleted Serious Gravity 10 4 instances 100 exposed
Issued
Mar 6, 2015
Abate by
Apr 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.219(i)(2): Revolving surfaces of shaft coupling(s) were not covered by a safety sleeve:  (a) Node #3 Return Belt: On or about January 20, 2015 and times prior, employees are exposed to caught in hazards of the exposed shaft coupling protruding bolts not covered by sleeve when transferring baggage.  (b) Node #5A Receiving Belt: On or about January 20, 2015 and times prior, employees are exposed to caught in hazards of the exposed shaft coupling protruding bolts not covered by sleeve when transferring baggage.  (c) Node #8 Inline Belt: On or about January 20, 2015 and times prior, employees are exposed to caught in hazards of the exposed shaft coupling protruding bolts not covered by sleeve when transferring baggage.  (d) Node #8 Clearance Belt: On or about January 20, 2015 and times prior, employees are exposed to caught in hazards of the exposed shaft coupling protruding bolts not covered by sleeve when transferring baggage.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 6 instances 100 exposed
Issued
Mar 6, 2015
Abate by
Apr 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) A/B Gate Supervisor Office: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to another relocatable power tap.  (b) Node 5A: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a refrigerator attached to a relocatable power tap.  (c) Node 5, Receiving Belt #9: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to a flexible cord.  (d) Node 5, Receiving Belt #10: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to a flexible cord.  (e) Gate C Breakroom: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to a flexible cord.  (f) Gate C Supervisor Office: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a refrigerator attached to a relocatable power tap.  (g) Terminal #3 Rest Area: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a microwave, coffee pot and toaster over attached to a relocatable power tap.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 1 instance 100 exposed
Issued
Mar 6, 2015
Abate by
Apr 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   (a) A/B Gate, Line #3: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire from the knockout missing from the power switch of the Smiths Detection Model 6040aTiX-2u baggage X-Ray machine.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02

Serious Gravity 5 1 instance 100 exposed
Issued
Mar 6, 2015
Abate by
Apr 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  (a) Gate C Breakroom: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using an electrical outlet with missing faceplate.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 4 instances 100 exposed
Issued
Mar 6, 2015
Abate by
Apr 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   (a) Node #3, Work Station #5: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a flexible cord to provide power to Uninterruptable Power Source (UPS).    (b) Node #5, Work Station #9: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a flexible cord to provide power to Uninterruptable Power Source (UPS).   (c) Node #5, Work Station #10: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a flexible cord to provide power to Uninterruptable Power Source (UPS).   (d) Node #5, Work Station #5: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a flexible cord to provide power to Uninterruptable Power Source (UPS).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 2 instances 40 exposed
Issued
Mar 6, 2015
Abate by
Apr 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:  (a) Behavioral Detection Office: On or about January 20, 2015 and at times prior, employees were exposed to electric shock/fire hazards by using a 120 volt Reloactable Power Tap that was run through a hole in the rear of a metal wall locker.  (b) A/B Gate, Supervisor Office: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire from a relocatable power tap and flexible cord that was concealed under the floor baseboard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 20 exposed
Issued
Mar 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  (a) Gate C Supervisor Office: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a refrigerator with a 120 volt flexible power cord with the outer sheath pulled away from the plug attachment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View U.S. Department of Homeland Security, Transportation Security Administration's full OSHA safety record →