LAS VEGAS, NV —
OSHA Inspection: U.S. DEPARTMENT OF HOMELAND SECURITY, TRANSPORTATION SECURITY ADMINISTRATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF HOMELAND SECURITY, TRANSPORTATION SECURITY ADMINISTRATION in 5757 WAYNE NEWTON BOULEVARD, LAS VEGAS, NV 89119 (NAICS 481111). OSHA activity number 340196799.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 5757 WAYNE NEWTON BOULEVARD
- City
- LAS VEGAS
- State
- NV
- ZIP
- 89119
- Mailing
- 6750 VIA AUSTI PARKWAY SUITE 200, LAS VEGAS, NV 89119
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 481111
- Employees
- 1150
- Ownership type
- D
Citations
7 citations on file for this inspection.
1910.219 I02
- Issued
- Mar 6, 2015
- Abate by
- Apr 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(i)(2): Revolving surfaces of shaft coupling(s) were not covered by a safety sleeve: (a) Node #3 Return Belt: On or about January 20, 2015 and times prior, employees are exposed to caught in hazards of the exposed shaft coupling protruding bolts not covered by sleeve when transferring baggage. (b) Node #5A Receiving Belt: On or about January 20, 2015 and times prior, employees are exposed to caught in hazards of the exposed shaft coupling protruding bolts not covered by sleeve when transferring baggage. (c) Node #8 Inline Belt: On or about January 20, 2015 and times prior, employees are exposed to caught in hazards of the exposed shaft coupling protruding bolts not covered by sleeve when transferring baggage. (d) Node #8 Clearance Belt: On or about January 20, 2015 and times prior, employees are exposed to caught in hazards of the exposed shaft coupling protruding bolts not covered by sleeve when transferring baggage.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Mar 6, 2015
- Abate by
- Apr 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) A/B Gate Supervisor Office: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to another relocatable power tap. (b) Node 5A: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a refrigerator attached to a relocatable power tap. (c) Node 5, Receiving Belt #9: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to a flexible cord. (d) Node 5, Receiving Belt #10: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to a flexible cord. (e) Gate C Breakroom: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to a flexible cord. (f) Gate C Supervisor Office: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a refrigerator attached to a relocatable power tap. (g) Terminal #3 Rest Area: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a microwave, coffee pot and toaster over attached to a relocatable power tap.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Mar 6, 2015
- Abate by
- Apr 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) A/B Gate, Line #3: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire from the knockout missing from the power switch of the Smiths Detection Model 6040aTiX-2u baggage X-Ray machine.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02
- Issued
- Mar 6, 2015
- Abate by
- Apr 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: (a) Gate C Breakroom: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using an electrical outlet with missing faceplate.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Mar 6, 2015
- Abate by
- Apr 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Node #3, Work Station #5: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a flexible cord to provide power to Uninterruptable Power Source (UPS). (b) Node #5, Work Station #9: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a flexible cord to provide power to Uninterruptable Power Source (UPS). (c) Node #5, Work Station #10: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a flexible cord to provide power to Uninterruptable Power Source (UPS). (d) Node #5, Work Station #5: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a flexible cord to provide power to Uninterruptable Power Source (UPS).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Mar 6, 2015
- Abate by
- Apr 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: (a) Behavioral Detection Office: On or about January 20, 2015 and at times prior, employees were exposed to electric shock/fire hazards by using a 120 volt Reloactable Power Tap that was run through a hole in the rear of a metal wall locker. (b) A/B Gate, Supervisor Office: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire from a relocatable power tap and flexible cord that was concealed under the floor baseboard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Mar 6, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) Gate C Supervisor Office: On or about January 20, 2015 and times prior, employees are exposed to electric shock/fire by using a refrigerator with a 120 volt flexible power cord with the outer sheath pulled away from the plug attachment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at U.S. Department of Homeland Security, Transportation Security Administration
More inspections in this industry (NAICS 481111)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340196799.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.