BOZEMAN, MT —
OSHA Inspection: QSC, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of QSC, INC. in 1922 WEST MAIN ST., BOZEMAN, MT 59715 (NAICS 722513). OSHA activity number 340201425.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- QSC, INC.
- Site address
- 1922 WEST MAIN ST.
- City
- BOZEMAN
- State
- MT
- ZIP
- 59715
- Mailing
- 522 WEST MAIN ST., BOZEMAN, MT 59715
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 722513
- Employees
- 40
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.37 A03
- Issued
- Jun 5, 2015
- Abate by
- Jul 1, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: (a) Cold storage: On or about January 21, 2015, and at times prior, employees were exposed to entrapment hazards while working in the kitchen area.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.38 B
- Issued
- Jun 5, 2015
- Abate by
- Jul 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.38(b): An emergency action plan was not in writing, kept in the workplace, and available to employees for review: (a) Facility: On or about January 21, 2015, and at times prior, employees were exposed entrapment hazards from the lack of an emergency action plan that outlined emergency evacuation procedures and duties.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Jun 5, 2015
- Abate by
- Jul 1, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Kitchen area: On or about January 21, 2015, and at time prior, employees were exposed to electrical burns and shock when the electrical junction box was not being used in the manner that it was designed.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.305 E01
- Issued
- Jun 5, 2015
- Abate by
- Jul 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: (a) Kitchen area: On or about January 21, 2015, and at time prior, employees were exposed shock hazards while using an unapproved outlet in a wet/damp location.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Jun 5, 2015
- Abate by
- Jul 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) Kitchen area: On or about January 21, 2015, and at time prior, employees were exposed to shock hazards while operating the bun toaster.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Jun 5, 2015
- Abate by
- Jul 1, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a) Kitchen area: On or about January 21, 2015, and at time prior, employees were exposed to the hazards associated with not being able to de-energize equipment in the event of an emergency.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.305 B01 II
- Issued
- Jun 5, 2015
- Abate by
- Jul 1, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) Kitchen area: On or about January 21, 2015, and at time prior, employees were exposed to shock and arc flash burns when the breaker panel had unguarded openings.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
More inspections at QSC, INC.
View QSC, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 722513)
More inspections in MT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340201425.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.