CARROLLTON, OH —
OSHA Inspection: COAL AUGER PRO
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of COAL AUGER PRO in 301 INDUSTRIAL DRIVE, CARROLLTON, OH 44615 (NAICS 333131). OSHA activity number 340202654.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COAL AUGER PRO
- Site address
- 301 INDUSTRIAL DRIVE
- City
- CARROLLTON
- State
- OH
- ZIP
- 44615
- Mailing
- 2234 ROSWELL ROAD, S.W., CARROLLTON, OH 44615
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 333131
- Employees
- 7
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.305 B01 II
- Issued
- Apr 7, 2015
- Penalty
- Initial $1,020 · Current $714 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. a. On or about January 23, 2015, located in the fabrication shop behind the horizontal band saw, there was a 177 volt electrical panel box that was used in part to supply electrical power to the shop's overhead lights which had knockouts that were not effectively closed, thereby exposing the employees to a burn injury if an arc flash would occur. b. On or about January 23, 2015, located in the fabrication shop behind the horizontal band saw, there was a 120 volt electrical panel box that was used in part to supply electrical power to the shop's receptacle outlets which had knockouts that were not effectively closed, thereby exposing the employees to a burn injury if an arc flash would occur.
Recent events (2)
- — I (S) $714
- — Z (S) $1020
1910.179 G01 IV
- Issued
- Apr 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.179(g)(1)(iv): Where multiple conductor cable is used with a suspended pushbutton station, the station must be supported in some satisfactory manner that will protect the electrical conductors against strain. a. On or about January 23, 2015, located in the East Bay on the 10 ton overhead crane, the employer did not ensure that a pendant control box (suspended pushbutton station) had strain relief provided at the point where the multiple conductor cable connected to the pendant control box.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 333131)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340202654.