Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AMERICAN REFINING GROUP, INC.

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of AMERICAN REFINING GROUP, INC. in 77 NORTH KENDALL AVENUE, BRADFORD, PA 16701 (NAICS 324110). OSHA activity number 340213859.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch American Refining Group, INC. — free Get an email when a new federal OSHA severe-injury report for American Refining Group, INC. is published. One employer, no account, unsubscribe in one click.
Site address
77 NORTH KENDALL AVENUE
City
BRADFORD
State
PA
ZIP
16701
Mailing
77 NORTH KENDALL AVENUE, BRADFORD, PA 16701
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
324110
Employees
350
Ownership type
A

6 citations on file for this inspection.

1910.333 A02

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 8, 2015
Abate by
Jul 20, 2015
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), work practices that were used were not suitable for the conditions under which the work was performed:  a.) American Refining Group, Inc. - On or about January 28, 2015 and at times prior thereto, safety-related work practices including, but not limited to, the use of appropriate electrically rated personal protective equipment, was not required and in use during installation of an Allen Bradley brand 480 Volt starter.  The 480V starter was being installed into the Crude Unit Motor Control Center which was not de-energized prior to installation of the motor starter.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.332 B01

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 8, 2015
Abate by
Jul 20, 2015
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:   a.) American Refining Group, Inc. - On or about January 28, 2015, and at times prior thereto, electricians were not trained in and familiar with the proper use of electrical related personal protective equipment during installation of an Allen Bradley brand 480 Volt starter.  The 480V starter was being installed into the Crude Unit Motor Control Center which was not de-energized prior to installation of the motor starter.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.333 C02

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 8, 2015
Abate by
Jul 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools:  a.) American Refining Group, Inc. - On or about January 28, 2015, and at times prior thereto, qualified persons were not familiar with the proper use of electrically related personal protective equipment during installation of an Allen Bradley brand 480 Volt starter.  The 480V starter was being installed into the Crude Unit Motor Control Center which was not de-energized prior to installation of the motor starter.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.137 C02 VIII

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 8, 2015
Abate by
Aug 24, 2015
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.137(c)(2)(viii): 29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-4 and I-5:  a.) American Refining Group, Inc. - On or about January 28, 2015, and at times prior thereto, electrical protective rubber insulating gloves were not inspected every 6 months.  Sets of gloves were identified that were last tested in 2009 and 2011.  b.) American Refining Group, Inc. - On or about January 28, 2015, and at times prior thereto, electrical protective rubber insulating blankets were not inspected every 12 months.  Blankets were identified that were last tested in 2008.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.137 C02 XII

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 8, 2015
Abate by
Aug 24, 2015
Penalty
Initial $0 · Current $0
1910.137(c)(2)(xii): The employer did not certify that electrical protective equipment had been tested in accordance with the requirements of paragraphs (c)(2)(iv), (c)(2)(vii)(D), (c)(2)(viii), (c)(2)(ix), and (c)(2)(xi) of this section.   a.) American Refining Group, Inc. - On or about January 28, 2015, and at times prior thereto, the employer had not certified that electrical protective equipment, including but not limited to gloves, sleeves, and insulating blankets, had been appropriately tested. The company was unable to provide such documentation upon request.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01

Serious Gravity 10 2 instances 3 exposed
Issued
Jul 8, 2015
Abate by
Jul 20, 2015
Penalty
Initial $70,000 · Current $7,000 Reduced
29 CFR 1910.335(a)(1): Employees working in areas where there were potential electrical hazards were not provided with, and/or did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:      a.) American Refining Group, Inc. - On or about January 28, 2015, and at times prior thereto, employees were not using appropriate electrical rated personal protective equipment including, but not limited to, arc flash hoods, gloves, sleeves, and insulating blankets, during installation of an Allen Bradley brand 480 Volt starter.  The 480V starter was being installed into the Crude Unit Motor Control Center which was not de-energized prior to the installation of the motor starter.  The appropriate electrical rated personal protective equipment for work involving energized equipment as required by the Employers SAF-26 procedure Electrical Safe Work Practices, and as referenced in the National Fire Protection Association (NFPA) 70E Table 130.7(c)(15)(A)(a), was not in use when the 480V motor starter was installed.
Recent events (2)
  • — I (S) $7000
  • — Z (W) $70000

View American Refining Group, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340213859.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.