GULFPORT, MS —
OSHA Inspection: TABER EXTRUSIONS, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of TABER EXTRUSIONS, LLC in 1900 34TH STREET, GULFPORT, MS 39501 (NAICS 331316). OSHA activity number 340214865.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TABER EXTRUSIONS, LLC
- Site address
- 1900 34TH STREET
- City
- GULFPORT
- State
- MS
- ZIP
- 39501
- Mailing
- 1900 34TH STREET, GULFPORT, MS 39501
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331316
- Employees
- 98
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.184 E01
- Issued
- Apr 29, 2015
- Abate by
- May 14, 2015
- Penalty
- Initial $3,443 · Current $0 Reduced
General-duty citation text
29 CFR 1910.184(e)(1): Alloy steel sling(s) did not have permanently affixed durable identification stating size, grade, rated capacity, and reach: (a) Casting - On or about January 26, 2015, the metal alloy sling used to remove castings did not have an identification tag with the size, grade, rated capacity and reach.
Recent events (2)
- — I (S) $0
- — Z (S) $3443
1910.253 A03
- Issued
- Apr 29, 2015
- Penalty
- Initial $2,754 · Current $2,754
General-duty citation text
29 CFR 1910.253(a)(3): Apparatus such as torches, regulators or pressure-reducing valves, acetylene generators, and manifolds used in an oxygen-fuel gas system had not been approved: (a) Back of the Milton press - On or about January 26, 2015, both gauges were damaged on the oxygen cylinder and the low pressure gauge on the propane cylinder mounted on the torch cart.
Recent events (2)
- — I (O) $2754
- — Z (S) $2754
1910.303 G02 I
- Issued
- Apr 29, 2015
- Penalty
- Initial $3,443 · Current $3,443
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: (a) Extrusion band saw in the back of the cast house - On or about January 26, 2015, the door to the control cabinet was left open exposing employees to live electrical parts. (b) Melton extruder between the billet oven and extruder - On or about January 26, 2015, there were open slots in the circuit breaker panel with live electrical parts.
Recent events (2)
- — I (S) $3443
- — Z (S) $3443
1910.305 B01 I
- Issued
- Apr 29, 2015
- Abate by
- May 14, 2015
- Penalty
- Initial $3,443 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering boxes, cabinets, or fittings were not protected from abrasions; (a) Slug saw - On or about January 26, 2015, the flexible conduit to the wall mounted exhaust fan was not attached to the fan motor allowing the conductors to be exposed to abrasions, cuts, and strains on the terminals and metal shavings entering the motor.
Recent events (2)
- — I (S) $0
- — Z (S) $3443
1910.22 A01
- Issued
- Apr 29, 2015
- Abate by
- May 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, and service rooms were not kept clean and orderly and in a sanitary condition: (a) Re-cut saw in extrusion - On or about January 26, 2015, metal shavings had accumulated on an enclosed electric motor to the hydraulic pump. (b) Slug saw - On or about January 26, 2015, metal shavings had accumulated on a receptacle on post A2 and on the electric motor for the hydraulic oil cooler.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 F02
- Issued
- Apr 29, 2015
- Abate by
- May 14, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a) Milton extruder between the billet oven and extruder - On or about January 26, 2015, the circuit breakers were not labeled or marked to indicate their purpose.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G02 III
- Issued
- Apr 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) Back of Milton press on the wall near the re-cut saw - On or about January 26, 2015, the flexible cord attached to a disconnect used for a double fan had a defective strain relief. Corrected during the inspection.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Taber Extrusions, LLC
View Taber Extrusions, LLC's full OSHA safety record →
More inspections in this industry (NAICS 331316)
More inspections in MS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340214865.