LIVERPOOL, NY —
OSHA Inspection: VANSANTIS DEVELOPMENT INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VANSANTIS DEVELOPMENT INC. in 4595 MORGAN PLACE, LIVERPOOL, NY 13090 (NAICS 321920). OSHA activity number 340257880.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VANSANTIS DEVELOPMENT INC.
- Site address
- 4595 MORGAN PLACE
- City
- LIVERPOOL
- State
- NY
- ZIP
- 13090
- Mailing
- 4595 MORGAN PLACE, LIVERPOOL, NY 13090
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321920
- Employees
- 40
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.36 H02
- Issued
- Feb 25, 2015
- Abate by
- Mar 5, 2015
- Penalty
- Initial $2,625 · Current $1,838 Reduced
General-duty citation text
29 CFR 1910.36(h)(2): Outdoor exit route was not covered where snow or ice was likely to accumulate. (Exception: Not required where employer can demonstrate that snow or ice will be removed before it can present a hazard): a) Maintenance Shop, on or about 2/3/15: There was snow accumulation along the exit route outside the exit door. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $1837.5
- — Z (S) $2625
1910.37 A03
- Issued
- Feb 25, 2015
- Abate by
- Mar 9, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) Pallet Shop, on or about 2/3/15: An exit door was not maintained free and unobstructed in that the door frame was in disrepair thus preventing opening of the exit door. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 G02
- Issued
- Feb 25, 2015
- Abate by
- Apr 1, 2015
- Penalty
- Initial $1,575 · Current $1,103 Reduced
General-duty citation text
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter: a) At the establishment, on or about 2/3/15: Annual training was not provide to employees on the use of fire extinguishers and the hazards involved with incipient stage fire fighting. *ABATEMENT NOTE: By this date the employer must either correct the alleged violation or implement a Fire Safety Policy as outlined in 29 CFR 1910.38 and 29 CFR 1910.39 which includes the evacuation requirements of 29 CFR 1910.157(b). Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $1102.5
- — Z (S) $1575
1910.304 G05
- Issued
- Feb 25, 2015
- Abate by
- Mar 9, 2015
- Penalty
- Initial $1,575 · Current $1,103 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) Maintenance Shop, on or about 2/3/15: Extension cord providing current to the fuel pump was not grounded in that the ground pin was missing from the plug end. b) Pallet Shop, on or about 2/3/15: An extension cord was not grounded in that the ground pin was missing from plug end. Abatement certification must be submitted for these items.
Recent events (2)
- — I (S) $1102.5
- — Z (S) $1575
1910.305 B02 I
- Issued
- Feb 25, 2015
- Abate by
- Mar 9, 2015
- Penalty
- Initial $1,575 · Current $1,103 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) Pallet Shop, on or about 2/3/15: The cover for a duplex receptacle outlet on the back wall was not secured in place exposing live electrical parts. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $1102.5
- — Z (S) $1575
1910.305 G01 IV A
- Issued
- Feb 25, 2015
- Abate by
- Apr 1, 2015
- Penalty
- Initial $1,575 · Current $1,103 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Maintenance Shop, on or about 2/3/15: Two extension cords providing current to a fuel pump were run from an outlet inside the building under an overhead door and were being used as permanent wiring. b) Break Room, on or about 2/3/15: Extension cord providing current to heat tape for the water pipe was strung along the floor and being used as permanent wiring. c) Maintenance Shop, on or about 2/3/15: A strip outlet and an extension cord attached to a workbench were being used as permanent wiring. Abatement certification must be submitted for these items.
Recent events (2)
- — I (S) $1102.5
- — Z (S) $1575
1910.305 G02 II
- Issued
- Feb 25, 2015
- Abate by
- Mar 9, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap: a) Pallet Shop, on or about 2/3/15: An orange extension cord had been spliced to a black extension cord. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A02 I
- Issued
- Feb 25, 2015
- Abate by
- Mar 9, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): a) Pallet Shop, on or about 2/3/15: An extension cord had damage to the outer jacket of the cord. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.242 B
- Issued
- Feb 25, 2015
- Abate by
- Mar 9, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: a) Pallet Shop, on or about 2/3/15: A compressed air gun used for cleaning purposes on the pallet building bench measured >100 psi. Abatement certification must be submitted for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Vansantis Development INC.
View Vansantis Development INC.'s full OSHA safety record →
More inspections in this industry (NAICS 321920)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340257880.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.