LA FERIA, TX —
OSHA Inspection: MID VALLEY SHEET METAL INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MID VALLEY SHEET METAL INC. in 13710 E BUSINESS HWY 83, LA FERIA, TX 78559 (NAICS 332312). OSHA activity number 340281245.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MID VALLEY SHEET METAL INC.
- Site address
- 13710 E BUSINESS HWY 83
- City
- LA FERIA
- State
- TX
- ZIP
- 78559
- Mailing
- PO BOX 276, LA FERIA, TX 78559
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332312
- Employees
- 5
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 F02
- Issued
- Apr 20, 2015
- Abate by
- May 18, 2015
- Penalty
- Initial $1,700 · Current $1,020 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: In the machine shop, electrical panel boxes and unlabeled circuit breakers such as but not limited to: a) West side machine shop area panel boxes attached to Lown Model B400 b) Machine shop area panel boxes attached to Lock Former-SL-135
Recent events (2)
- — I (S) $1020
- — Z (S) $1700
1910.305 B01 II
- Issued
- Apr 20, 2015
- Abate by
- May 18, 2015
- Penalty
- Initial $1,700 · Current $1,020 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: At this location employees working on lathes and drills were exposed to electrical hazards due to missing knockouts on electrical panels such as but not limited to: a) West side of machine shop lighting panel box. b) Lock former - SL - 135
Recent events (2)
- — I (S) $1020
- — Z (S) $1700
1910.305 G02 III
- Issued
- Apr 20, 2015
- Abate by
- May 18, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: At this location employees working on welding machines and metal bending fabrication equipment were exposed to electrical hazards due to broken conduit exposing electrical wires: a) Syncrowave200 b) Industrial fan mounted to wall on west side of machine shop c) Lincoln LN electric Power located in machine shop d) BPR Curvatric located in machine shop
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at MID Valley Sheet Metal INC.
View MID Valley Sheet Metal INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332312)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340281245.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.