Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FEDERAL MEDIATION AND CONCILIATION SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FEDERAL MEDIATION AND CONCILIATION SERVICE in 2001 6TH AVENUE SUITE 2500, SEATTLE, WA 98121 (NAICS 922130). OSHA activity number 340344621.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Federal Mediation and Conciliation Service — free Get an email when a new federal OSHA severe-injury report for Federal Mediation and Conciliation Service is published. One employer, no account, unsubscribe in one click.
Site address
2001 6TH AVENUE SUITE 2500
City
SEATTLE
State
WA
ZIP
98121
Mailing
2001 6TH AVENUE SUITE 2500, SEATTLE, WA 98121
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922130
Employees
9
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 4 instances 5 exposed
Issued
Feb 24, 2015
Abate by
Mar 29, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a)  Room 2521;  A relocatable power tap was plugged into another relocatable power tap. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not  daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.   (b)  Room 2519;  A relocatable power tap was plugged into another relocatable power tap. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.   (c)  Room 2518;  A relocatable power tap was plugged into an extension cord. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.   (d)  Room 2501, Kitchen; A Delonghi coffee pot, BraAun coffee grinder and Oster toaster oven were plugged into a relocatable power tap. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances.  This exposes employees to possible electrical fire hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G02 I D

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 24, 2015
Abate by
Mar 29, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i)(D): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by elevation of 2.44 m (8.0 ft) or more above the floor or other working surface:  a) Storage closet adjacent to conference room;  An unguarded florescent light bulb was located 6 feet 9 inches from the floor.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Feb 24, 2015
Abate by
Mar 29, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a)       Room 2520;  An electrical outlet in the conference room was missing a cover.
Recent events (1)
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340344621.