Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: KEMPER CONSOLIDATED INDUSTRIES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of KEMPER CONSOLIDATED INDUSTRIES, INC. in 423 ENTERPRISE LANE, CANTON, IL 61520 (NAICS 332439). OSHA activity number 340403187.

Watch Kemper Consolidated Industries, INC. — free Get an email when a new federal OSHA severe-injury report for Kemper Consolidated Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
423 ENTERPRISE LANE
City
CANTON
State
IL
ZIP
61520
Mailing
PO BOX 492, CANTON, IL 61520
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332439
Employees
13
Ownership type
A

6 citations on file for this inspection.

1910.22 A01

Serious Gravity 1 1 instance 10 exposed
Issued
Penalty
Initial $1320.00 · Current $924.00 Reduced
29 CFR 1910.22(a)(1):  All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition.    Employees were exposed to tripping hazards because the Contain Box/Retrievals Repair Area was not kept clear of tripping hazards, because the employer had not taken the necessary steps to remove the forklift magnet from the area.
Recent events (2)
  • — I (S) $924
  • — Z (S) $1320

1910.37 B05

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $1760.00 · Current $1232.00 Reduced
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):    Employees were exposed to fire, smoke inhalation, slips, trips, and falls hazards in the event of an emergency because the closet door in the Contain Box/Retrievals Repair Area could be mistaken for an exit, because the closet door was not marked "Not an Exit"
Recent events (2)
  • — I (S) $1232
  • — Z (S) $1760

1910.303 G01 I

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $1320.00 · Current $924.00 Reduced
29 CFR 1910.303(g)(1)(i):  The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1:   Employees were exposed to electrical shock  hazards in the event that the electrical panel on the south wall needed to be accessed, because a 36-inch wide working space was not maintained in front of panel.
Recent events (2)
  • — I (S) $924
  • — Z (S) $1320

1910.305 B01 I

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $1760.00 · Current $1232.00 Reduced
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed:  Employees using the circuit panel on the south wall were exposed to electrical shock hazards because the panel had openings for conductors that were not effectively closed adjacent to the switches for the lights.
Recent events (2)
  • — I (S) $1232
  • — Z (S) $1760

1910.305 B01 II

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   Employees using the circuit panel on the south wall were exposed to electrical hazards because the panel had an unused opening and was not effectively closed (a breaker had been removed).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Penalty
Initial $1760.00 · Current $1232.00 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  Employees working in the Contain Box/Retrieval Repair Area were exposed to electrical hazards because the dead front cover or other approved enclosure was missing on the south wall circuit panel.
Recent events (2)
  • — I (S) $1232
  • — Z (S) $1760

View KEMPER CONSOLIDATED INDUSTRIES, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340403187.