Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TEC ELECTRICAL CONTRACTING, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TEC ELECTRICAL CONTRACTING, INC. in 1133 BLACK ROCK RD, PHOENIXVILLE, PA 19460 (NAICS 238210). OSHA activity number 340405851.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch TEC Electrical Contracting, INC. — free Get an email when a new federal OSHA severe-injury report for TEC Electrical Contracting, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1133 BLACK ROCK RD
City
PHOENIXVILLE
State
PA
ZIP
19460
Mailing
340-B ANDREWS ROAD, TREVOSE, PA 19053
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
23
Ownership type
A

3 citations on file for this inspection.

1926.405 A02 II E

Serious Gravity 1 4 instances 12 exposed
Issued
Mar 16, 2015
Penalty
Initial $867 · Current $306 Reduced
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage:    a) Construction site, multiple locations - On or about February 4, 2015, employees were exposed to potential injury from temporary lighting that was not protected from accidental contact or breakage.
Recent events (2)
  • — I (S) $306
  • — Z (S) $867

1926.405 B02

Serious Gravity 1 1 instance 12 exposed
Issued
Mar 16, 2015
Penalty
Initial $867 · Current $306 Reduced
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy:    a) Construction site, 2nd floor - On or about February 4, 2015, Employees used tools and equipment plugged into 120V duplex outlets that did not have faceplates installed.
Recent events (2)
  • — I (S) $306
  • — Z (S) $867

1926.417 B

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 16, 2015
Penalty
Initial $2,040 · Current $2,040
29 CFR 1926.417(b): Equipment or circuits that were de-energized did not have tags attached at all points where such equipment or circuits could be energized:  a) Construction site, Room 240 - On or about February 2, 2015 employees installing wiring to a fan control unit were exposed to injury from an energized circuit that had not been tagged out or rendered inoperative, and was accidentally re-energized.