Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: SKAGIT VALLEY CASINO RESORT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SKAGIT VALLEY CASINO RESORT in 5984 N. DARRK LANE, BOW, WA 98232 (NAICS 721120). OSHA activity number 340417450.

Watch Skagit Valley Casino Resort — free Get an email when a new federal OSHA severe-injury report for Skagit Valley Casino Resort is published. One employer, no account, unsubscribe in one click.
Site address
5984 N. DARRK LANE
City
BOW
State
WA
ZIP
98232
Mailing
5984 N. DARRK LANE, BOW, WA 98232
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721120
Employees
468
Ownership type
A

5 citations on file for this inspection.

1910.215 B09

Serious Gravity 1 1 instance 4 exposed
Issued
Penalty
Initial $1721.00 · Current $1200.00 Reduced
29 CFR 1910.215(b)(9):The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:     a) Facility Work Shop, where the tongue guard on the Dayton pedestal grinder measured 1/2 inch from the abrasive wheel.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $1721

1910.303 B02

Serious Gravity 1 3 instances 4 exposed
Issued
Abate by
Penalty
Initial $2025.00 · Current $1400.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling:    a)  Facility, where electrical equipment not used as listed or labeled included:    1. Card and Dice Room, where the job made extension cord (handy box) was daisy chained with an orange extension cord and used to supply power to the box docking station.     2. Facility Work Shop, where two permanently mounted relocatable power taps were daisy chained and used to supply power to equipment including the Grizzly table saw and battery chargers.    3. Facility Work Shop, where seven relocatable power taps were daisy chained with the Tripp-Lite multiple outlet strip and used to supply power to the GE microwave oven and the batteries in the APC and Cyber Power uninterrupted power source (UPS) units.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2025

1910.305 G01 IV A

Serious Gravity 1 3 instances 100 exposed
Issued
Abate by
Penalty
Initial $2025.00 · Current $1400.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:   a) Facility, where flexible cords used as a substitute for fixed wiring included:     1. Card and Dice Room, where an orange extension cord was used to supply power to the box docking station. (Item Corrected)     2. Employee Dining Room and Kitchen, where an orange extension cord was used to supply power to the Profile microwave oven.    3. Skillet Kitchen, where a brown extension cord was used to supply power to the Amana microwave oven and the radio. (Item Corrected)
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2025

1910.37 B02

Other-than-serious 1 instance 100 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(2):  Each exit was not clearly visible and marked by a sign reading "Exit":  a) Southeast Hotel Exit, where the door that opened into the exit access was not equipped with an exit sign.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.333 B02 I

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:  a) Facility Work Shop, where employees repaired electrical equipment including, but not limited to, ballast in florescent lighting and outlets.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View SKAGIT VALLEY CASINO RESORT's full OSHA safety record →