MIDDLE GRANVILLE, NY —
OSHA Inspection: K-D STONE INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of K-D STONE INC. in ROUTE 22, MIDDLE GRANVILLE, NY 12849 (NAICS 327991). OSHA activity number 340425719.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- K-D STONE INC.
- Site address
- ROUTE 22
- City
- MIDDLE GRANVILLE
- State
- NY
- ZIP
- 12849
- Mailing
- ROUTE 22, MIDDLE GRANVILLE, NY 12849
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327991
- Employees
- 8
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.305 J04 II
- Issued
- Apr 6, 2015
- Abate by
- Apr 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(4)(ii): An individual disconnecting means was not provided for each controller and located within sight of the controller location. However, a single disconnecting means may be located adjacent to a group of coordinated controllers mounted adjacent to each other on a multi-motor continuous process machine. The controller disconnecting means for motor branch circuits over 600 volts, nominal, may be out of sight of the controller, if the controller is marked with a warning label giving the location and identification of the disconnecting means that is to be locked in the open position. (a) Saw room, motor disconnect(s): On or prior to 2/25/15, Two 240v fused safety disconnects (knife switches) for motor control branch circuits were by-passed; main disconnect for branch circuit(s)was located in a panel in the splitting room. Abatement note: (1) A single disconnecting means may be located adjacent to a group of coordinated controllers mounted adjacent to each other on a multi-motor continuous process machine. The controller disconnecting means for motor branch circuits over 600 volts, nominal, may be out of sight of the controller, if the controller is marked with a warning label giving the location and identification of the disconnecting means that is to be locked in the open position. (2) A motor controller does not meet the requirement for a disconnecting means.
Recent events (1)
- — Z (O) $0
More inspections at K-D Stone INC.
View K-D Stone INC.'s full OSHA safety record →
More inspections in this industry (NAICS 327991)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340425719.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.