OSHA Inspection: U.S. POSTAL SERVICE-OAKLAND PD&C

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of U.S. POSTAL SERVICE-OAKLAND PD&C in 1675 7TH STREET, OAKLAND, CA 94615 (NAICS 491110). OSHA activity number 340439702.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Postal Service-Oakland PD&C — free Get an email when a new federal OSHA severe-injury report for U.S. Postal Service-Oakland PD&C is published. One employer, no account, unsubscribe in one click.
Site address
1675 7TH STREET
City
OAKLAND
State
CA
ZIP
94615
Mailing
P.O. BOX 889017, OAKLAND, CA 94615
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
491110
Employees
1500
Ownership type
A

2 citations on file for this inspection.

1910.307 C

Serious Gravity 5 1 instance 100 exposed
Issued
Apr 6, 2015
Abate by
Sep 15, 2016
Penalty
Initial $5,500 · Current $5,500
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:     Facility: On March 5, 2015, employees were exposed to explosion hazards when Class II paper dust accumulation was being cleaned up by vacuum cleaners which were not intrinsically safe or approved for Class II Division E/F/G locations.
Recent events (2)
  • — Z $5500
  • — Z (S) $5500

1910.304 G05

Repeat 1 instance 1 exposed
Issued
Apr 6, 2015
Abate by
Apr 30, 2015
Penalty
Initial $220 · Current $220
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  Third Floor, DBCS Machines: Maintenance employees were exposed to electrical shock and explosion hazards when they used a Pullman Holt Shop Vacuum (Model 45, 120 volt, serial #24667) to pick up Class II combustible dust which was missing its ground prong.  The U.S. Postal Service was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.304(g)(5), which was contained in OSHA inspection number 390144, citation number 02, item number 003 and was affirmed as a final order on July 30, 2012, with respect to a workplace located at 3131 Arch Airport Road, Stockton, CA 95213.
Recent events (1)
  • — Z (R) $220

View U.S. Postal Service-Oakland PD&C's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340439702.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.