MCALLEN, TX —
OSHA Inspection: PALMER STEEL SUPPLIES INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PALMER STEEL SUPPLIES INC in 4300 ACAPULCO AVE, MCALLEN, TX 78503 (NAICS 332311). OSHA activity number 340448356.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PALMER STEEL SUPPLIES INC
- Site address
- 4300 ACAPULCO AVE
- City
- MCALLEN
- State
- TX
- ZIP
- 78503
- Mailing
- 4300 ACAPULCO AVE, MCALLEN, TX 78503
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332311
- Employees
- 162
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.23 D01 III
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $3,060 · Current $1,836 Reduced
General-duty citation text
29 CFR 1910.23(d)(1)(iii): Stairway(s) less than 44 inches wide having both sides open, did not have one stair railing on each side: At this worksite, the stairs that were used by employees at the roller conveyors did not have stair railings on either sides. There are three areas throughout the shop area to include: a) East of building first one at north end b) East of building second one towards north end c) East of building third on towards north end
Recent events (2)
- — I (S) $1836
- — Z (S) $3060
1910.179 G01 V
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $3,825 · Current $2,295 Reduced
General-duty citation text
29 CFR 1910.179(g)(1)(v): Pendant control box(es) were not clearly marked for identification of functions: At this worksite, several of the pendants that operate the Gantry cranes were not clearly marked of their functions such as but not limited to: a) Bay 3C b) Bay 4C
Recent events (2)
- — I (S) $2295
- — Z (S) $3825
1910.303 G02 I
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $6,300 · Current $3,780 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): At this worksite, in the area where the air compressor is installed, an open circuit box had exposed wires and an open enclosure where an employee worked.
Recent events (2)
- — I (S) $3780
- — Z (S) $6300
1910.305 B01 II
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $3,825 · Current $2,295 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: At this worksite, electrical panel boxes had missing knock-out holes that were open and not being utilized. Such as but not limited to: a) Northeast corner of work facility. All safety switches were unlabeled on the wall side by side.
Recent events (2)
- — I (S) $2295
- — Z (S) $3825
1910.303 F02
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: At this worksite, there were four service circuit breakers that had no labeling on the outside to identify where the energy was being serviced.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $3,060 · Current $1,836 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables may not be used where run through holes in walls, ceilings or floors: At this worksite, flexible cords were being run through holes in walls that are made of aluminum such as but not limited to: a) At the bandsaw area on the east side of the worksite near the roller conveyor tables. b) At the bandsaw area on the east side of the worksite next to the drill and press machine.
Recent events (2)
- — I (S) $1836
- — Z (S) $3060
1910.305 G02 III
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $3,060 · Current $1,836 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: At this worksite, a pendant that controls the overhead Gantry cranes had no strain relief installed as well as a switch box at the bottom of it as well. These locations are located at: a)Saw and drill area at the east side of the worksite building. b)Underneath the roller conveyor table at the east side of the worksite.
Recent events (2)
- — I (S) $1836
- — Z (S) $3060
More inspections at Palmer Steel Supplies INC
View Palmer Steel Supplies INC's full OSHA safety record →
More inspections in this industry (NAICS 332311)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340448356.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.