Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SIC RECYCLING, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SIC RECYCLING, INC. in 2200 OVERPASS ROAD, RIVERTON, IL 62561 (NAICS 423930). OSHA activity number 340457902.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch SIC Recycling, INC. — free Get an email when a new federal OSHA severe-injury report for SIC Recycling, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
SIC RECYCLING, INC.
Site address
2200 OVERPASS ROAD
City
RIVERTON
State
IL
ZIP
62561
Mailing
2200 OVERPASS ROAD, RIVERTON, IL 62561
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423930
Employees
25
Ownership type
A

7 citations on file for this inspection.

1910.147 C06 I

Serious Gravity 10 1 instance 5 exposed
Issued
Aug 12, 2015
Abate by
Sep 30, 2015
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1910.147(c)(6)(i):     The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    Employees were exposed to hazardous energy when performing servicing and maintenance tasks on the employers machinery and the periodic inspection did not include a review of the energy control procedures with each authorized employee.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1910.147 C06 II

Serious Gravity 10 1 instance 10 exposed
Issued
Aug 12, 2015
Abate by
Sep 30, 2015
Penalty
Initial $0 · Current $0
1910.147(c)(6)(ii):       The periodic inspection certification of energy control procedures did not contain the required documentation on identification of the machine or equipment, inspection date, employees included, and the person performing the inspection:    Employees were exposed to hazardous energy when performing servicing and maintenance tasks because the employer did not document periodic inspections and record the identification of the machine or equipment, inspection date, names of the employees included in the inspection and the name of the person performing the inspection.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 25 exposed
Issued
Aug 12, 2015
Abate by
Aug 24, 2015
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1910.305(b)(2):       Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:       Employees were exposed to the hazard of    electrical shock, due to the fact that an electrical junction box was left uncovered exposing the inner conductors.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1910.305 G01 IV A

Serious Gravity 5 1 instance 25 exposed
Issued
Aug 12, 2015
Abate by
Aug 24, 2015
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1910.305(g)(1)(iv)(A):      Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Employees working in the operations area were exposed to electrical and fire hazards because a cord used to provide power to a heat tapes on the dust collector was used as a substitute for fixed wiring.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1910.305 G01 IV B

Serious Gravity 5 1 instance 25 exposed
Issued
Aug 12, 2015
Abate by
Aug 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B):      Flexible cords and/or cables were run through holes in walls, ceilings, or floors:       Employees working in the operations area were exposed to electrical hazards because the electrical cord used to provide power to the heat tapes on the dust collector was run through a hole in the corrugated steel wall.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 5 1 instance 25 exposed
Issued
Aug 12, 2015
Abate by
Aug 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D):      Flexible cords and/or cables were attached to building surfaces:    Employees working in the operations area were exposed to electrical and fire hazards because a cord used to provide power to the heat tapes on the dust collector was attached to the building and with zip-ties and electrical tape.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 5 exposed
Issued
Aug 12, 2015
Abate by
Aug 24, 2015
Penalty
Initial $1,600 · Current $0 Reduced
29 CFR 1910.305(g)(2)(iii):      Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:     Employees were exposed to the hazard of electrical shock when using the extension cord powering the heat tapes because the conductors were not connected with devices and fittings that would have prevented tension from being transmitted to the them.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1600