RIVERTON, IL —
OSHA Inspection: SIC RECYCLING, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SIC RECYCLING, INC. in 2200 OVERPASS ROAD, RIVERTON, IL 62561 (NAICS 423930). OSHA activity number 340457902.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SIC RECYCLING, INC.
- Site address
- 2200 OVERPASS ROAD
- City
- RIVERTON
- State
- IL
- ZIP
- 62561
- Mailing
- 2200 OVERPASS ROAD, RIVERTON, IL 62561
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423930
- Employees
- 25
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.147 C06 I
- Issued
- Aug 12, 2015
- Abate by
- Sep 30, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: Employees were exposed to hazardous energy when performing servicing and maintenance tasks on the employers machinery and the periodic inspection did not include a review of the energy control procedures with each authorized employee.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.147 C06 II
- Issued
- Aug 12, 2015
- Abate by
- Sep 30, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.147(c)(6)(ii): The periodic inspection certification of energy control procedures did not contain the required documentation on identification of the machine or equipment, inspection date, employees included, and the person performing the inspection: Employees were exposed to hazardous energy when performing servicing and maintenance tasks because the employer did not document periodic inspections and record the identification of the machine or equipment, inspection date, names of the employees included in the inspection and the name of the person performing the inspection.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Aug 12, 2015
- Abate by
- Aug 24, 2015
- Penalty
- Initial $1,600 · Current $800 Reduced
General-duty citation text
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: Employees were exposed to the hazard of electrical shock, due to the fact that an electrical junction box was left uncovered exposing the inner conductors.
Recent events (2)
- — I (S) $800
- — Z (S) $1600
1910.305 G01 IV A
- Issued
- Aug 12, 2015
- Abate by
- Aug 24, 2015
- Penalty
- Initial $1,600 · Current $800 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Employees working in the operations area were exposed to electrical and fire hazards because a cord used to provide power to a heat tapes on the dust collector was used as a substitute for fixed wiring.
Recent events (2)
- — I (S) $800
- — Z (S) $1600
1910.305 G01 IV B
- Issued
- Aug 12, 2015
- Abate by
- Aug 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: Employees working in the operations area were exposed to electrical hazards because the electrical cord used to provide power to the heat tapes on the dust collector was run through a hole in the corrugated steel wall.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Aug 12, 2015
- Abate by
- Aug 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and/or cables were attached to building surfaces: Employees working in the operations area were exposed to electrical and fire hazards because a cord used to provide power to the heat tapes on the dust collector was attached to the building and with zip-ties and electrical tape.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Aug 12, 2015
- Abate by
- Aug 24, 2015
- Penalty
- Initial $1,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: Employees were exposed to the hazard of electrical shock when using the extension cord powering the heat tapes because the conductors were not connected with devices and fittings that would have prevented tension from being transmitted to the them.
Recent events (2)
- — I (S) $0
- — Z (S) $1600
More inspections at SIC Recycling, INC.
View SIC Recycling, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 423930)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340457902.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.